Carrier 50EY User Manual
Page 7
NOTES:
1. Weights include economizer (Std)
2.
Center of gravity.
3. Do not locate adjacent units with discharge facing economizer inlet.
Minimum clearances to be:
Adjacent Units: 15
Ј
-0
Љ
Top of Units: No overhang
Condenser Coil: 4
Ј
-0
Љ
Economizer Side: 6
Ј
-0
Љ
Filter Access Side: 10
Ј
-0
Љ
(for removal of evaporator coil)
4. For smaller service and operational clearances, contact Carrier
Application Engineering department.
5. Dimensions are in inches. Dimensions in [
] are in millimeters.
6. For units equipped with electric heat, a field-supplied 90° elbow must
be installed in the supply ductwork below the unit discharge.
7. For side-supply/return applications, a single return and supply duct-
work connection is recommended for covering both return and both
supply air openings.
UNIT SIZE
50E
OPERATING
WEIGHT
(lb)
A
B
CORNER WEIGHT
(lb)
ft-in.
ft-in.
1
2
3
4
W038
4282
7-7
5
⁄
16
3-10
1
⁄
2
961 858 1162 1302
W/Y044
4508
7-3
13
⁄
16
3-11
1
⁄
2
973 868 1258 1409
W048
4795
7-2
3
⁄
16
3-10
3
⁄
32
1007 915 1368 1505
Fig. 6 — Base Unit Dimensions, 50EW038-048 and 50EY044
LEGEND
VFD — Variable Frequency Drive
7