Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)
UNIT
SIZE
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
No. 1
No. 2
Min
Max
RLA
LRA
RLA
LRA
Qty
Hp
FLA (ea)
Hp
FLA
FLA
LRA
kW
FLA
MCA
MOCP†
038
208/230
187
254
57.1
266
57.1
266
4
1
5.3
10
30.8/
28.0
—
—
—
—
180.5/177.7
225/225
23.6
41.6
—
—
204.1/201.3
250/250
—
—
29/36
75.1/ 86.6
180.5/177.7
225/225
23.6
41.6
29/36
75.1/ 86.6
204.1/201.3
250/250
—
—
59/72
150.1/173.2
188.6/208.2
225/225
23.6
41.6
59/72
150.1/173.2
218.1/237.7
250/250
15
46.2/
42.0
—
—
—
—
195.9/191.7
250/225
23.6
41.6
—
—
219.5/215.3
275/250
—
—
29/36
75.1/ 86.6
195.9/191.7
250/225
23.6
41.6
29/36
75.1/ 86.6
219.5/215.3
275/250
—
—
59/72
150.1/173.2
207.9/225.7
250/250
23.6
41.6
59/72
150.1/173.2
237.4/255.2
275/275
20
59.4/
54.0
—
—
—
—
209.1/203.7
250/250
23.6
41.6
—
—
232.7/227.3
275/275
—
—
29/36
75.1/ 86.6
209.1/203.7
250/250
23.6
41.6
29/36
75.1/ 86.6
232.7/227.3
275/275
—
—
59/72
150.1/173.2
224.4/240.7
275/275
23.6
41.6
59/72
150.1/173.2
253.9/270.2
300/300
460
414
508
25.6
120
25.6
120
4
1
2.7
10
14
—
—
—
—
82.4
100
12.6
23.6
—
—
95.0
110
—
—
36
43.3
82.4
100
12.6
23.6
36
43.3
95.0
110
—
—
72
86.6
104.1
110
12.6
23.6
72
86.6
119.9
125
15
21
—
—
—
—
89.4
110
12.6
23.6
—
—
102.0
125
—
—
36
43.3
89.4
110
12.6
23.6
36
43.3
102.0
125
—
—
72
86.6
112.9
125
12.6
23.6
72
86.6
128.6
150
20
27
—
—
—
—
95.4
110
12.6
23.6
—
—
108.0
125
—
—
36
43.3
95.4
110
12.6
23.6
36
43.3
108.0
125
—
—
72
86.6
120.4
125
12.6
23.6
72
86.6
136.1
150
575
518
632
20.5
96
20.5
96
4
1
2.4
10
11
—
—
—
—
66.7
80
12.6
23.6
—
—
79.3
90
—
—
36
34.6
66.7
80
12.6
23.6
36
34.6
79.3
90
—
—
72
69.3
83.0
90
12.6
23.6
72
69.3
98.8
100
15
17
—
—
—
—
72.7
90
12.6
23.6
—
—
85.3
100
—
—
36
34.6
72.7
80
12.6
23.6
36
34.6
85.3
100
—
—
72
69.3
90.5
100
12.6
23.6
72
69.3
106.3
110
20
22
—
—
—
—
77.7
90
12.6
23.6
—
—
90.3
110
—
—
36
34.6
77.7
90
12.6
23.6
36
34.6
90.3
110
—
—
72
69.3
96.8
110
12.6
23.6
72
69.3
112.5
125
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.
If power distribution voltage to unit varies from rated heater voltage, heater kW will
vary accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +
(1.00 x heater FLA).
21