Carrier 50EY User Manual
Page 20

Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)
UNIT
SIZE
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
No. 1
No. 2
Min
Max
RLA
LRA
RLA
LRA
Qty
Hp
FLA (ea)
Hp
FLA
FLA
LRA
kW
FLA
MCA
MOCP†
034
208/230
187
254
57.1
266
57.1
266
2
1
5.3
10
30.8/
28.0
—
—
—
—
169.9/167.1
225/200
23.6
41.6
—
—
193.5/190.7
250/225
—
—
29/36
75.1/ 86.6
169.9/167.1
225/200
23.6
41.6
29/36
75.1/ 86.6
193.5/190.7
250/225
—
—
59/72
150.1/173.2
188.6/208.2
225/225
23.6
41.6
59/72
150.1/173.2
218.1/237.7
250/250
15
46.2/
42.0
—
—
—
—
185.3/181.1
225/225
23.6
41.6
—
—
208.9/204.7
250/250
—
—
29/36
75.1/ 86.6
185.3/181.1
225/225
23.6
41.6
29/36
75.1/ 86.6
208.9/204.7
250/250
—
—
59/72
150.1/173.2
207.9/225.7
250/250
23.6
41.6
59/72
150.1/173.2
237.4/255.2
275/275
20
59.4/
54.0
—
—
—
—
198.5/193.1
250/250
23.6
41.6
—
—
222.1/216.7
275/250
—
—
29/36
75.1/ 86.6
198.5/193.1
250/250
23.6
41.6
29/36
75.1/ 86.6
222.1/216.7
275/250
—
—
59/72
150.1/173.2
224.4/240.7
275/275
23.6
41.6
59/72
150.1/173.2
253.9/270.2
300/300
460
414
508
25.6
120
25.6
120
2
1
2.7
10
14
—
—
—
—
77.0
100
12.6
23.6
—
—
89.6
110
—
—
36
43.3
77.0
100
12.6
23.6
36
43.3
89.6
110
—
—
72
86.6
104.1
110
12.6
23.6
72
86.6
119.9
125
15
21
—
—
—
—
84.0
100
12.6
23.6
—
—
96.6
110
—
—
36
43.3
84.0
100
12.6
23.6
36
43.3
96.6
110
—
—
72
86.6
112.9
125
12.6
23.6
72
86.6
128.6
150
20
27
—
—
—
—
90.0
110
12.6
23.6
—
—
102.6
125
—
—
36
43.3
90.0
110
12.6
23.6
36
43.3
103.6
125
—
—
72
86.6
120.4
125
12.6
23.6
72
86.6
136.1
150
575
518
632
20.5
96
20.5
96
2
1
2.4
10
11
—
—
—
—
61.9
80
12.6
23.6
—
—
74.5
90
—
—
36
34.6
61.9
70
12.6
23.6
36
34.6
74.5
90
—
—
72
69.3
83.0
90
12.6
23.6
72
69.3
98.8
100
15
17
—
—
—
—
67.9
80
12.6
23.6
—
—
80.5
100
—
—
36
34.6
67.9
80
12.6
23.6
36
34.6
80.5
100
—
—
72
69.3
90.5
100
12.6
23.6
72
69.3
106.3
110
20
22
—
—
—
—
72.9
90
12.6
23.6
—
—
85.5
100
—
—
36
34.6
72.9
90
12.6
23.6
36
34.6
86.6
100
—
—
72
69.3
96.8
110
12.6
23.6
72
69.3
112.5
125
20