NOTES:
1. Weights include economizer (Std)
2.
Center of gravity.
3. Do not locate adjacent units with dis-
charge facing economizer inlet. Mini-
mum clearances to be:
Adjacent Units: 15
Ј
-0
Љ
Top of Units: No overhang
Condenser Coil: 4
Ј
-0
Љ
Economizer Side: 6
Ј
-0
Љ
Filter Access Side: 10
Ј
-0
Љ
(for re-
moval of evaporator coil)
4. For smaller service and operational
clearances, contact Carrier Applica-
tion Engineering department.
5. Bottom ducts designed to be attached
to accessory roof curb. If unit is mounted
on dunnage, it is recommended the
ducts be supported by cross braces as
done on accessory roof curb.
6. Dimensions are in inches. Dimen-
sions in [
] are in millimeters.
7. For units with electric heat, a field-
supplied 90° elbow must be installed
in the supply ductwork below the unit
discharge.
LEGEND
VFD — Variable Frequency Drive
UNIT SIZE
50EJ/EK
OPERATING
WEIGHT
(lb)
A
B
CORNER WEIGHT
(lb)
ft-in.
ft-in.
1
2
3
4
024
4016
5-11
3
⁄
8
3-5
11
⁄
16
823
914
1199
1080
028
4102
5- 8
1
⁄
2
3-7
5
⁄
8
844
859
1210
1189
030
4102
5- 8
1
⁄
2
3-7
5
⁄
8
844
859
1210
1189
034
4102
5- 8
1
⁄
2
3-7
5
⁄
8
844
859
1210
1189
Fig. 3 — Base Unit Dimensions, 50EJ/EK024-034
4