NOTES:
1. Weights include economizer (Std)
2.
Center of gravity.
3. Do not locate adjacent units with discharge facing economizer inlet. Mini-
mum clearances to be:
Adjacent Units: 15
Ј
-0
Љ
Top of Units: No overhang
Condenser Coil: 4
Ј
-0
Љ
Economizer Side: 6
Ј
-0
Љ
Filter Access Side: 10
Ј
-0
Љ
(for removal of evaporator coil)
4. For smaller service and operational clearances, contact Carrier Applica-
tion Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
mounted on dunnage, it is recommended the ducts be supported by cross
braces as done on accessory roof curb.
6. Dimensions are in inches. Dimensions in [
] are in millimeters.
7. For units with electric heat, a field-supplied 90° elbow must be installed
in the supply ductwork below the unit discharge.
UNIT SIZE
50E
OPERATING
WEIGHT
(lb)
A
B
CORNER WEIGHT
(lb)
ft-in.
ft-in.
1
2
3
4
J038
4282
7-7
5
⁄
16
3-10
1
⁄
2
961
858
1162
1302
J/K044
4508
7-3
13
⁄
16
3-11
1
⁄
2
973
868 1258 1409
J048
4795
7-2
3
⁄
16
3-10
3
⁄
32
1007
915
1368
1505
Fig. 4 — Base Unit Dimensions, 50EJ038-048 and 50EK044
LEGEND
VFD — Variable Frequency Drive
5