Table 16 — motor limitations, Table 17 — user defined set points – Carrier 50EY User Manual
Page 39
Table 16 — Motor Limitations
STANDARD EFFICIENCY MOTORS
Nominal
Hp
Maximum
Bhp
Maximum Amps
Maximum
Watts
Motor
Efficiency
208
230
460
575
5
5.9
17.94
16.99
—
—
5,348
82.3
5.9
—
—
8.50
5.78
5,240
84.0
7.5
8.7
25.52
24.36
—
—
7,717
84.1
9.5
—
—
13.30
9.63
8,549
82.9
10
10.2
26.93
25.50
—
—
8,879
85.7
11.8
—
—
14.75
11.33
10,284
85.6
15
15.3
42.84
40.80
—
—
13,686
83.4
18.0
—
—
24.00
18.00
15,891
84.5
20
22.4
59.36
56.00
—
—
19,032
87.8
23.4
—
—
29.25
22.82
19,950
87.5
25
28.9
76.30
72.83
—
—
24,499
88.0
29.4
—
—
37.04
28.69
25,181
87.1
30
35.6
92.56
87.81
—
—
29,378
90.4
34.7
—
—
42.80
n/a
29,316
88.3
HIGH EFFICIENCY MOTORS
Nominal
Hp
Maximum
Bhp
Maximum Amps
Maximum
Watts
Motor
Efficiency
208
230
460
575
5
5.9
16.76
13.92
—
—
5,030
87.5
5.9
—
—
6.96
—
5,030
87.5
5.9
—
—
—
5.66
4,918
89.5
7.5
8.7
26.10
22.27
—
—
7,334
88.5
9.5
—
—
12.16
—
8,008
88.5
9.5
—
—
—
9.50
7,728
91.7
10
10.2
28.56
24.89
—
—
8,502
89.5
11.8
—
—
14.40
—
9,836
89.5
11.8
—
—
—
11.68
9,600
91.0
15
15.3
45.08
39.17
—
—
12,543
91.0
18.0
—
—
23.04
—
14,756
91.0
18.0
—
—
—
18.12
14,439
93.0
20
22.4
63.84
55.55
—
—
18,363
91.0
23.4
—
—
29.02
—
19,183
91.0
23.4
—
—
—
23.17
18,650
93.6
25
28.9
80.69
70.05
—
—
23,511
91.7
29.4
—
—
35.63
—
23,918
91.7
29.4
—
—
—
28.81
23,432
93.6
30
35.6
102.65
89.00
—
—
28,742
92.4
34.7
—
—
43.38
—
28,015
92.4
34.7
—
—
—
33.89
27,656
93.6
LEGEND
BHP — Brake Horsepower
NOTE: Extensive motor and electrical testing on the Carrier units has ensured
that the full horsepower range of the motor can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown on the Motor Limi-
tations table will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
Table 17 — User Defined Set Points
SET POINT
FORMAT
DESCRIPTION
LIMITS
DEFAULT
OHSP
xx.xF
Occupied Heat Set Point
55 to 80 F
68
OCSP
xx.xF
Occupied Cool Set Point
55 to 80 F
78
UHSP
xx.xF
Unoccupied Heat Set Point
40 to 80 F
55
UCSP
xx.xF
Unoccupied Cool Set Point
75 to 95 F
90
SASP
xx.xF
Supply Air Set Point
45 to 70 F
55
OATL
xx.xF
Hi OAT Lockout Temperature
55 to 75 F
65
NTLO
xx.xF
Unoccupied OAT Lockout Temperature
40 to 70 F
50
RTIO
xx.x
Reset Ratio
0 to 10
3
LIMT
xx.x^F
Reset Limit
0 to 20 F
10
MDP
xxx%
Minimum Damper Position
0 to 100%
20
IAQS
xxxx
IAQ Set Point
1 to 5000
650
UHDB
xx.x^F
Unoccupied Heating Deadband
0 to 10
1
UCDB
xx.x^F
Unoccupied Cooling Deadband
0 to 10
1
LTMP
xx.xF
Low Temp. Min. Position
0 to 100
10
HTMP
xx.xF
High Temp. Min. Position
0 to 100
35
PES1
xx.xF
CV Power Exhaust Stage 1 Point
0 to 100
25
PES2
xx.xF
CV Power Exhaust Stage 2 Point
0 to 100
75
LEGEND
CV
— Constant Volume
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
39