Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048
UNIT
SIZE
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
No. 1
No. 2
Min
Max
RLA
LRA
RLA
LRA
Qty
Hp
FLA (ea)
Hp
FLA
FLA
LRA
kW
FLA
MCA
MOCP†
024
208/230
187
254
39.1
228
25.6
160
2
1
5.3
5
16.7/
15.2
—
—
—
—
101.8/100.3
125/125
23.6
41.6
—
—
125.4/123.9
150/150
—
—
29/36
75.1/ 86.6
114.7/127.3
125/150
23.6
41.6
29/36
75.1/ 86.6
144.2/156.8
150/175
—
—
59/72
150.1/173.2
171.0/192.2
200/225
23.6
41.6
59/72
150.1/173.2
200.5/221.7
225/225
10
30.8/
28.0
—
—
—
—
115.9/113.1
150/150
23.6
41.6
—
—
139.5/136.7
175/175
—
—
29/36
75.1/ 86.6
132.3/143.3
150/150
23.6
41.6
29/36
75.1/ 86.6
161.8/172.8
175/175
—
—
59/72
150.1/173.2
188.6/208.2
220/225
23.6
41.6
59/72
150.1/173.2
218.1/237.7
250/250
15
46.2/
42.0
—
—
—
—
131.3/127.1
150/150
23.6
41.6
—
—
154.9/150.7
175/175
—
—
29/36
75.1/ 86.6
151.6/160.8
175/175
23.6
41.6
29/36
75.1/ 86.6
181.1/190.3
200/200
—
—
59/72
150.1/173.2
207.9/225.7
250/250
23.6
41.6
59/72
150.1/173.2
237.4/255.2
275/275
460
414
508
19.9
114
11.5
80
2
1
2.7
5
7.6
—
—
—
—
49.4
60
12.6
23.6
—
—
62.0
80
—
—
36
43.3
63.6
70
12.6
23.6
36
43.3
79.4
80
—
—
72
86.6
96.1
110
12.6
23.6
72
86.6
111.9
125
10
14
—
—
—
—
55.8
70
12.6
23.6
—
—
68.4
80
—
—
36
43.3
71.6
80
12.6
23.6
36
43.3
87.4
90
—
—
72
86.6
104.1
110
12.6
23.6
72
86.6
119.9
125
15
21
—
—
—
—
62.8
80
12.6
23.6
—
—
75.4
90
—
—
36
43.3
80.4
90
12.6
23.6
36
43.3
96.1
100
—
—
72
86.6
112.9
125
12.6
23.6
72
86.6
128.6
150
575
518
632
16.0
91
9.6
64
2
1
2.4
5
6.1
—
—
—
—
40.5
50
12.6
23.6
—
—
53.1
60
—
—
36
34.6
50.9
60
12.6
23.6
36
34.6
66.7
70
—
—
72
69.3
76.9
80
12.6
23.6
72
69.3
92.7
100
10
11
—
—
—
—
45.4
60
12.6
23.6
—
—
58.0
70
—
—
36
34.6
57.1
60
12.6
23.6
36
34.6
72.8
80
—
—
72
69.3
83.0
90
12.6
23.6
72
69.3
98.8
100
15
17
—
—
—
—
51.4
60
12.6
23.6
—
—
64.0
80
—
—
36
34.6
64.6
70
12.6
23.6
36
34.6
80.3
90
—
—
72
69.3
90.5
100
12.6
23.6
72
69.3
106.3
110
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.
If power distribution voltage to unit varies from rated heater voltage, heater kW will
vary accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +
(1.00 x heater FLA).
17