Wine Guardian Wine Cellar Cooling Systems 50Hz (WG 175) User Manual
Page 35

Advanced Settings--
Special access required.
Contact Wine Guardian
Service Department for
access code
Setting 8
Press “Mode” button to advance to Setting 8.
Press the up or down arrow buttons to adjust
number to the access code. Press “Mode” button to
continue onto setting 9 through 19.
Compressor anti-short
cycling time
Setting 9
Press “Mode” button to advance to Setting 9.
Press the “Up” or “Down” arrow buttons to adjust
to the desired time in one (1) minute increments.
Maximum is 10 minutes, minimum is 0 minutes.
Compressor anti-short cycling time is the amount of
allowable time between compressor stop and restart.
Rapid start/stop of compressors can cause premature
failure. Factory default is 5 minutes.
WINE GUARDIAN DOES NOT RECOMMEND
SETTINGS LOWER THAN FACTORY DEFAULT.
Set up remote sensor
or thermostat
Setting 10
Press “Mode” button to advance to Setting 10.
Press the “Up” or “Down” arrow buttons to adjust
to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit only
A = Averaging – Jumper position within sensors
must be adjusted. See page 27.
Room sensor
calibration
Setting 15
Press “Mode” button to advance to Setting 15.
Press the “Up” or “Down” buttons to adjust to the
desired set point. Maximum setting is +2°C,
minimum setting is -2°C. Factory default is zero
(0). Sensor calibration set point changes the actual
display reading (temperature only) by the value of
this setting.
Example: Sensor reading = 13 Deg C
Setting 15 set to +2
Display reading = 15 Deg C
32