beautypg.com

Vintage Cellars Split System CellarPro User Manual

Page 33

background image


 

33

Maintenance

The condenser coils on the Condensing unit will collect dust, dirt and lint over time. If
the condenser coils become clogged, the cooling unit will not have proper airflow
and its performance and longevity will be compromised. The condenser coils
themselves also can be cleaned with a vacuum cleaner – ideally with a brush
attachment to loosen dust caught between the fins.

Alarms

The cooling unit has both an audible notification and a visual alarm indicator (shown in
“red” on the control panel) that are activated when an alarm is triggered. Please note:
the temperature alarms (HA and LA) are disabled during the first 23 hours of operation
after the cooling unit is plugged in and/or turned on.
The control panel also will flash a code for each alarm, as follows:

Alarm Code

What it means

What to do

P1

Probe 1, which

senses the

temperature inside

the cellar and

controls the on/off

cycles of the cooling

unit, has failed

The cooling unit enters a timed auto-

cycle mode until Probe 1 is repaired or

replaced. In this mode, the cooling unit

will turn on for 12 minutes and off for 8

minutes.
Please call CellarPro at 877.726.8496

to repair or replace Probe 1

HA

The temperature

inside the cellar is

too warm (above

70°F for more than

1 hour)

Check if the cellar has a leak

Check if door was left open

Lower the ambient temperatures

LA The

temperature

inside the cellar is too

cold (below 45°F)

Raise the ambient temperature

Raise the “Minimum Set Point”