Up and Down Buttons 
 
To view the “High Temp” recorded by the 
cooling unit, press the “Up” button once. 
To view the “Low Temp” recorded by the 
cooling unit, press the “Down” button once. 
 
To reset the “High Temp” or “Low Temp”, 
press the “Set” button for three seconds 
while “Hi” or “Lo” is displayed. “RST” will 
blink three times to indicate confirmation. 
Set Button
The cooling unit is factory preset with a 
Minimum Set Point of 58°F and a 
Temperature Differential of 4°F. This 
means that the cooling unit will turn on 
when the display rises above 62°F (58°F + 
4°F), and turn off when the display falls 
below 58°F. In this example, the average 
temperature inside the cellar will be 60°F. 
 
To view the Minimum Set Point, press the 
“Set” button for one second. 
 
To change the Minimum Set Point, 
 Press the “Set” button for three
seconds until °F” blinks
 Press “Up” or “Down” button 
 Press “Set” button to confirm 
 
The “Set” temperature will blink three times 
to indicate confirmation 
 
The recommended Minimum Set Point 
range is 53 - 60°F. To change the 
Temperature Differential, see “Advanced 
Operation” later in this chapter. 