19

Power On/Off Button

Press “Power On/Off” to turn the unit on and off

When the “Compressor On” indicator light is on, the
Compressor is running. When the “Fan On” indicator
light is on, the Fan is running

Up and Down Buttons

To view the “High Temp” recorded by the cooling unit,
press the “Up” button once.

To view the “Low Temp” recorded by the cooling unit,
press the “Down” button once

To reset the “High Temp” or “Low Temp”, press the
“Set” button for three seconds while “Hi” or “Lo” is
displayed. “RST” will blink three times to indicate
confirmation.

Set Button

The cooling unit is factory preset with a Minimum Set
Point of 58°F and a Temperature Differential of 4°F. This
means that the cooling unit will turn on when the display
rises above 62°F (58°F + 4°F), and turn off when the
display falls below 58°F. In this example, the average
temperature inside the cellar will be 60°F.

To view the Minimum Set Point, press the “Set” button
for one second.

To change the Minimum Set Point,

1. Press the “Set” button for three seconds until “°F”

blinks

2. Press the “Up” or “Down” button
3. Press the “Set” button to confirm

The “Set” temperature will blink three times to indicate
confirmation.

The recommended Minimum Set Point range is 53 - 60°F.
To change the Temperature Differential, see “Advanced
Operation” later in this chapter.