BYPASS TEST PROCEDURE

1. Disconnect power from the evaporator unit
2. Loosen the two screws on the front of the grille or duct plenum
3. Pull the grill or duct plenum away from the evaporator unit
4. Remove the screw securing the control panel in place
5. Slide the control panel down, out of the evaporator housing. The control panel has two hooks which

allow it to attach to the evaporator unit for easy serviceability.

6. Disconnect the Molex connector labeled #4.
7. Locate the bypass plug included in the accessory kit.
8. Plug the bypass plug into the male Molex connector.
9. Connect power to the evaporator unit. The unit should immediately turn on. If all the components are

not operational, disconnect power immediately and contact customer service. If all components seem

to be operating correctly, allow the unit to run for 4 hours. Monitor the temperature of the cellar to

determine if the unit is cooling properly.

10. Once the test is complete, remove the bypass plug. Plug the Molex connector back in to the unit’s wiring.
11. Replace the control and faceplate.

NOTE: If instructed by a WhisperKool representative, follow the directions below to test the cooling unit using the

bypass plug provided in the accessory kit.