Vintage Cellars CellarPro Owners Manual User Manual

Page 25

background image

24

If the cooling unit continues to drip, contact us at 1.877.726.8496 for further
assistance.

• The HA2 Alarm has been triggered

The cooling unit is designed to measure the temperature of the condenser coils and,
if the temperature exceeds 125°F for more than 2 hours, the HA2 alarm will display
on the control panel.

If this alarm happens when you first receive and start operating your CellarPro
cooling unit, check for appropriate installation and ventilation (Chapter II). Also,
make sure that there aren’t any obstructions to the intake and/or exhaust vents. If

your wine cabinet has a grill, remove the grill and/or any other obstructions above
(top vent) or behind (back vent) the cellar.

If the alarm happens in conjunction with hot ambient conditions, we recommend
doing the following:

1. Raise the Minimum Set Point to 60°F until temperatures cool down
2. Increase the Fon setting

If the cooling has been operating for several months without any problems and the
alarm happens “out of the blue”, check the condenser coils and clean if necessary.

If the HA2 alarm continues to be triggered, contact us at 1.877.726.8496 for further
assistance.

• The LA2 Alarm has been triggered

As noted above, the cooling unit is designed to measure the temperature of the
condenser coils and, if the temperature drops below a certain poing, the LA2 alarm

will display on the control panel. To reduce the alarm temperature setting, do the
following:

1. Depress the “Set” and “Down” button for three seconds until the display

reads “HY”

2. Depress the “Set” and “Down” button (again) for seven seconds until “PR2”

flashes on the display

3. Using the “Down” button, scroll until the display reads “AL2”
4. Depress the “Set” button and lower the alarm temperature setting to your

desired temperature