Vintage Cellars CellarPro Owners Manual User Manual
Page 25

24
If the cooling unit continues to drip, contact us at 1.877.726.8496 for further
assistance.
• The HA2 Alarm has been triggered
The cooling unit is designed to measure the temperature of the condenser coils and,
if the temperature exceeds 125°F for more than 2 hours, the HA2 alarm will display
on the control panel.
If this alarm happens when you first receive and start operating your CellarPro
cooling unit, check for appropriate installation and ventilation (Chapter II). Also,
make sure that there aren’t any obstructions to the intake and/or exhaust vents. If
your wine cabinet has a grill, remove the grill and/or any other obstructions above
(top vent) or behind (back vent) the cellar.
If the alarm happens in conjunction with hot ambient conditions, we recommend
doing the following:
1. Raise the Minimum Set Point to 60°F until temperatures cool down
2. Increase the Fon setting
If the cooling has been operating for several months without any problems and the
alarm happens “out of the blue”, check the condenser coils and clean if necessary.
If the HA2 alarm continues to be triggered, contact us at 1.877.726.8496 for further
assistance.
• The LA2 Alarm has been triggered
As noted above, the cooling unit is designed to measure the temperature of the
condenser coils and, if the temperature drops below a certain poing, the LA2 alarm
will display on the control panel. To reduce the alarm temperature setting, do the
following:
1. Depress the “Set” and “Down” button for three seconds until the display
reads “HY”
2. Depress the “Set” and “Down” button (again) for seven seconds until “PR2”
flashes on the display
3. Using the “Down” button, scroll until the display reads “AL2”
4. Depress the “Set” button and lower the alarm temperature setting to your
desired temperature