PROTECTION — Once the units are properly positioned on

the jobsite, they must be covered with either a shipping carton,

vinyl film, or an equivalent protective covering. Open ends of

pipes stored on the jobsite must be capped. This precaution is

especially important in areas where painting, plastering, or

spraying of fireproof material, etc., is not yet complete. Foreign

material that is allowed to accumulate within the units can pre-

vent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to

examine each pipe, fitting, and valve, and remove any dirt or

foreign material found in or on these components.

INSPECT UNIT — To prepare the unit for installation, com-

plete the procedures listed below:

1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the

correct unit has been shipped.

2. Verify that the unit is the correct model for the entering

water temperature of the job.

3. Wait to remove the packaging until the unit is ready for

installation.

4. Verify that the refrigerant tubing is free of kinks or dents,

and that it does not touch other unit components.

5. Inspect all electrical connections. Be sure connections are

clean and tight at the terminals.

6. Loosen bolts and remove shipping clamps on compres-

sors equipped with external spring vibration isolators.

Compressors are internally spring-mounted.

7. Locate and verify any accessory kit located in compressor

section.

31.3

38.1

11.4

10.8

Power Supply Wiring
34.9 x 50.8 mm Double Knockout

10.8

Control Wiring

28.6 x 34.9 mm Double Knockout

11.4

2” FPT Water Connections

38.1

13.8

53.3

Fault/Run Lights

163.8

Left
Side
View

Front

View

Top

View

Load

Source

Side

Refrig.

Circuit

Access

Panel

Front

Compressor

Access

Panel

Electrical

Access

Panel

Header
Access

Panel

Top

Minimum 91cm

Required Service

Access

114.6

66.9

Optional (Single Unit)

91cm Additional

Service Access

Fig. 2 — 50PSW180,360 Unit

LEGEND
FPT — Female Pipe Thread

NOTES:

1. Dimensions shown in centimeters unless noted other-

wise.

2. For multiple units placed side by side, allow 1.2 m mini-

mum front access for service and maintenance.

CAUTION

DO NOT store or install units in corrosive environments or

in locations subject to temperature or humidity extremes

(e.g., attics, garages, rooftops, etc.). Corrosive conditions

and high temperature or humidity can significantly reduce

performance, reliability, and service life. Always move

units in an upright position. Tilting units on their sides may

cause equipment damage.