21 table 13 — troubleshooting – Carrier AQUAZONE 50PSW036-360 User Manual
Page 21
![background image](/manuals/64032/21/background.png)
21
Table 13 — Troubleshooting
LEGEND
FAULT
HEATING
COOLING
POSSIBLE CAUSE
SOLUTION
Main Power Problems
X
X
Green Status LED Off
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24-vac between R and C on controller.
Check primary/secondary voltage on transformer.
HP Fault — Code 2
High Pressure
X
Reduced or no water flow in
cooling
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
X
Water temperature out of range
in cooling
Bring water temperature within design parameters.
X
X
Overcharged with refrigerant
Check superheat/subcooling vs. typical operating condition.
X
X
Bad HP switch
Check switch continuity and operation. Replace.
LP/LOC Fault — Code 3
Low Pressure/Loss of
Charge
X
X
Insufficient charge
Check for refrigerant leaks.
X
Compressor pump down at
start-up
Check charge and start-up water flow.
FP1 Fault — Code 4
Source Water Freeze
Protection
X
Reduced or no water flow in
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Inadequate antifreeze level
Check antifreeze density with hydrometer.
X
Improper freeze protect setting
(–1.1 C vs –12.2 C)
Clip JW3 jumper for antifreeze (–12.2 C) use.
X
Water temperature out of range
Bring water temperature within design parameters.
X
X
Bad thermistor
Check temperature and impedance correlation.
FP2 Fault — Code 5
Load Coil Freeze
Protection
X
Reduced or no water flow in
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Improper freeze protect setting
(–1.1 C vs –12.2 C)
Clip JW3 jumper for antifreeze (–12.2 C) use.
X
Water temperature out of range
Bring water temperature within design parameters.
X
X
Bad thermistor
Check temperature and impedance correlation.
Over/Under Voltage —
Code 7
(Auto Resetting)
X
X
Under voltage
Check power supply and 24-vac voltage before and during operation.
Check power supply wire size.
Check compressor starting.
Check 24-vac and unit transformer tap for correct power supply voltage.
X
X
Over voltage
Check power supply voltage and 24-vac before and during operation.
Check 24-vac and unit transformer tap for correct power supply voltage.
Performance Monitor —
Code 8
X
Heating mode FP2>51.7 C
Check for overcharged unit.
X
Cooling mode FP1>51.7 C OR
FP2< 4.4 C
Check for poor water flow or airflow.
No Fault Code Shown
X
X
No compressor operation
See scroll compressor rotation section.
X
X
Compressor overload
Check and replace if necessary.
X
X
Control board
Reset power and check operation.
Unit Short Cycles
X
X
Unit in Test mode
Reset power or wait 20 minutes for auto exit.
X
X
Unit selection
Unit may be oversized for space. Check sizing for actual load of space.
X
X
Compressor overload
Check and replace if necessary.
Unit Does Not Operate in
Cooling
X
Reversing valve
Set for cooling demand and check 24-vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while operat-
ing engage and disengage RV coil voltage to push valve.
X
Thermostat setup
Check for ‘O’ RV setup not ‘B’.
X
Thermostat wiring
Check O wiring at heat pump. Jumper O and R for RV coil.
Insufficient Capacity/
Not Cooling or Heating
Properly
X
X
Low refrigerant charge
Check superheat and subcooling.
X
X
Restricted metering device
Check superheat and subcooling. Replace.
X
Defective reversing valve
Perform RV touch test.
X
X
Thermostat improperly located
Check location and for air drafts behind thermostat.
X
X
Unit undersized
Recheck loads and sizing. Check sensible cooling load and heat pump
capacity.
X
X
Scaling in water heat exchanger Perform scaling check and clean if necessary.
X
X
Inlet water too hot or cold
Check load, loop sizing, loop backfill, ground moisture.
High Head Pressure
X
Scaling in water heat exchanger Perform scaling check and clean if necessary.
X
X
Unit overcharged
Check superheat and subcooling. Reweigh in charge.
X
X
Non-condensables in system
Vacuum system and reweigh in charge.
X
X
Restricted metering device
Check superheat and subcooling. Replace.
Low Suction Pressure
X
Reduced water flow in heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Water temperature out of range
Bring water temperature within design parameters.
FP
— Freeze Protection
HP
— High Pressure
LED — Light-Emitting Diode
LOC — Loss of Charge
LP
— Low Pressure
RV
— Reversing Valve