0 grounding, 1 ground rod locations, Grounding – Rice Lake RailBoss Rail Scales - Installation Manual User Manual
Page 12

8
Railboss Railroad Track Scale
4.0
Grounding
Rice Lake Weighing Systems strongly recommends installation of the RailBoss grounding system to protect the
RailBoss Railroad Track Scale from surges. Rail track scales of all types can be exposed to surges or lightning that
may hit the rail at even very long distances from the scale. It is recommended that scale sections be isolated from
the rail track on both ends of each section. Eight-foot ground rods should be driven between the rails, and a copper
wire connected to the rail on each side with a 10-gauge copper wire. Rail joint bar isolators (included) should also
be installed at each end of RailBoss sections.
Replacement Part Numbers
Table 4-1. Rail Joint Bar Isolator Kits
Part Number
Description
126111
Rail Joint Bar Isolator kit, 90 RE Full or Double Draft
112702
Rail Joint Bar Isolator kit, 115 RE Full or Double Draft
119771
Rail Joint Bar Isolator kit, 132 RE Full or Double Draft
Table 4-2. Grounding Kit Part Numbers
Part Number
Description
Grounding Kit Contents (Qty)
119800
Grounding kit, 115 lb RE Double Draft
110812, UPS Sola S1K520, (1)
119913, 8’ Copper bonded steel ground rod (2)
119916, Ground rod clamp (2)
119917, Pipe clamp, grounding (4)
119920, Copper wire, 10 ga. 25’ (1)
119801
Grounding kit, 115 lb RE Full Draft
119802
Grounding kit, 132 lb RE Double Draft
119803
Grounding kit, 132 lb RE Full Draft
4.1
Ground Rod Locations
Ground rod placement can vary depending on ground hardness; however, 8
'
ground rods should be installed near
the center of the track. See Figure 4-1 and 4-2 for recommended ground rod locations.
Ground rod
Isolators
Isolators
Figure 4-1. Ground Rod Locations in Double-Draft System
Ground rod
Isolators
Isolators
Figure 4-2. Ground Rod Locations in Full-Draft System