Table 4-2:Deviation of the Airflow Rate on the AM4204

Inlet Velocity

Deviation (%)

CFM

m/s

LFM

ZONE A

ZONE B

ZONE C

ZONE D

5

0.57

112.8

-8.08

6.03

5.21

-3.16

10

1.15

225.7

-5.95

3.90

4.72

-2.67

15

1.72

338.5

-4.92

3.28

3.83

-2.19

20

2.29

451.4

-84.21

2.77

3.59

-2.15

25

2.87

564.2

-3.76

2.45

3.44

-2.13

30

3.44

677.1

-3.48

2.25

3.34

-2.12

Note:

The Mid-size AM4204 module has an airflow rate deviation of max. ± 8.1% of the average value of
the four thermal zones (max. ± 25% is allowed).
Positive deviation means increased airflow.
Negative deviation means decreased airflow.