5.1.2.1.7
Kontron User SW upgradeStatus
5.1.2.2
Sensor Thresholds
Following table shows sensor thresholds for voltages
Table 5-8:Voltage sensor thresholds
5.1.2.3
Health Error
The Health Error is asserted if one of the sensors mentioned in Table 5-8 on page 41 (Voltage sensor
thresholds) exceeds UC, UNR, LC or LNR or one of the sensors mentioned in Table 4-1 (Temperature Sensor
Thresholds) in Chapter 4.1 exceeds UC or UNR.
Table 5-7:Kontron user SW upgrade status sensor
Event/Reading type
code
Sensor type
Sensor specific offset Event trigger
6Fh
CAh
OEM Kontron
External
Component
Firmware Upgrade
Status
00h
Firmware Upgrade in Progress (no event)
01h
Firmware upgrade succeeded
02h
Firmware upgrade failed
SENSOR Number / ID string
Lower Non-Re-
coverable
Lower criti-
cal
Lower non
critical
Upper non
critical
Upper crit-
ical
Upper Non-Re-
coverable
ID=15: Vcc 1.0V
na
1.01 V
1.03 V
1.18 V
1.294 V
na
ID=16: Vcc 1.0V BCM (AM4220
and AM4210 only)
na
0.88 V
0.93 V
1.08 V
1.465 V
na
ID=17: Vcc 1.1V
na
1.01 V
1.02 V
1.18 V
1.67 V
na
ID=18: Vcc 1.2V
na
1.10 V
1.13 V
1.28 V
1.29 V
na
ID=19: Vcc 1.8V
na
1.65 V
1.68 V
1.92 V
2.06 V
na
ID=20: Vcc 3.3v
na
3.05 V
3.06 V
3.55 V
3.56 V
na
ID=21: Vcc 3.3V SUS
na
2.92 V
2.93 V
3.69 V
3.70 V
na
ID=23: Vcc 12v
na
8.36 V
9.7 V
14.45 V
15.52 V
na