beautypg.com

48e s – Carrier SEER 48ES User Manual

Page 5

background image

5

Gask et around

outer edge

Insulated

deck

pan

Gask et around

duct

S/A

R/A

HVAC

unit

base

*Gask eting

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant str ip

field supplied

*Provided with roof curb

Roof

Ductwork

field supplied

Insulation (field

supplied)

Roof curb*

Wood nailer*

Gask eting

inner flange*

Scre w

(NO TE A)

Roof Curb for Small Cabinet

Note A: When unit mounting scre w is used,

retainer bra cke t must also be used.

HVAC unit

base

*Gask eting

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant str ip

field supplied

*Provided with roof curb

Roof

Ductwork

field supplied

Insulation (field

supplied)

Roof curb*

Wood nailer*

Gask eting

inner flange*

Scre w

(NOTE A)

Roof Curb for

Large Cabinet

Note A: When unit mounting scre w is used,

retainer bra cket

must also be used.

A

B Typ.

Supply opening

(B x C)

Long

Support

D

F

Return opening

(B X C)

Insulated

deck pan

Short

Support

C Typ.

G

E

F

G

D

E

A05308

UNIT SIZE

CATALOG

NUMBER

A

IN. (MM)

B

IN. (MM)

C

IN. (MM)

D

IN. (MM)

E

IN. (MM)

F

IN. (MM)

G

IN. (MM)

48ES024--036

CPRFCURB006A00

8 (203)

11 (279)

16--1/2 (419)

28--3/4 (730)

30--3/8 (771)

44--5/16 (1126)

45--15/16 (1167)

CPRFCURB007A00

14 (356)

11 (279)

16--1/2 (419)

28--3/4 (730)

30--3/8 (771)

44--5/16 (1126)

45--15/16 (1167)

48ES042--060

CPRFCURB008A00

8 (203)

16--3/16 (411)

17--3/8 (441)

40--1/4 (1022) 41--15/16 (1065)

44--7/16 (1129)

46--1/16 (1169)

CPRFCURB009A00

14 (356) 16--3/16 (411)

17--3/8 (441)

40--1/4 (1022) 41--15/16 (1065)

44--7/16 (1129)

46--1/16 (1169)

NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16---gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1---in. (25.4 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used (see Note A), a retainer bracket must

be used as well. This bracket must also be used when required by code for

hurricane or seismic conditions. This bracket is available through Micrometl.

Fig. 5 -- Roof Curb Dimensions

48E

S