Warning, Pre--start--up – Carrier SEER 48ES User Manual

Page 12

background image

12

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L3 to yellow wire on connection 13 of

the compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

Special Procedures for 208--v Operation

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Make sure the power supply to the unit is switched OFF and

install lockout tag. before making any wiring changes. With

disconnect switch open, move black wire from transformer

(3/16 in. [4.8 mm]) terminal marked 230 to terminal marked

208. This retaps transformer to primary voltage of 208 vac.

!

WARNING

ELECTRICAL SHOCK FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury or death and property damage.
Before making any wiring changes, make sure the gas

supply is switched off first. Then switch off the power

supply to the unit and install lockout tag.

!

WARNING

Control Voltage Connections

Do not use any type of power--stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35_C minimum) wires to make the control voltage connections

between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the

control voltage wires), use no. 16 AWG color--coded, insulated

(35_C minimum) wires.

Standard Connection

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

EQUIP GR

3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

W

Y

G

R

C

WHT(W1)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

A08205

Fig. 11 -- High-- and Control--Voltage Connections

Run the low--voltage leads from the thermostat, through the inlet
hole, and into unit low--voltage splice box.
Locate five 18--gage wires leaving control box. These low--voltage

connection leads can be identified by the colors red, green, yellow,
brown, and white (See Fig. 11). Ensure the leads are long enough

to be routed into the low--voltage splice box (located below right
side of control box). Route leads through hole in bottom of control

box and make low--voltage connections (See Fig. 11). Secure all
cut wires, so that they do not interfere with operation of unit.

Heat Anticipator Setting

The room thermostat heat anticipator must be properly adjusted to

ensure proper heating performance. Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact

required setting.
NOTE: For thermostat selection purposes, use 0.18 amp for the
approximate required setting. Failure to make a proper heat
anticipator adjustment will result in improper operation, discomfort
to the occupants of the conditioned space, and inefficient energy
utilization; however, the required setting may be changed slightly
to provide a greater degree of comfort for a particular installation.

Transformer Protection

The transformer is of the energy--limiting type, however a direct
short will likely blow a secondary fuse. If an overload or short is

present, correct overload condition and check for blown fuse on

Indoor Fan board or Integrated Gas Controller. Replace fuse as
required with correct size and rating.

PRE--START--UP

ENVIRONMENTAL,

FIRE,

EXPLOSION,

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Do not operate compressor or provide any electric power

to unit unless compressor plug is in place and secured.

3. Do not remove ccompressor plug until all electrical

sources are disconnected and tagged.

4. Relieve and recover all refrigerant from system before

touching or disturbing compressor plug if refrigerant
leak is suspected around compressor terminals.

5. Never attempt to repair soldered connection while

refrigerant system is under pressure.

6. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.
To remove a component, wear protective goggles and

proceed as follows:

a. Shut off electrical power to unit and install

lockout tag.

b. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch
flame.

!

WARNING

48E