Manual_ProfibusDPV2_BIDE_EN.docx

31/41

Baumer IVO GmbH & Co. KG

22.11.12

Villingen-Schwenningen, Germany

6.9.11. I&M parameter 65000 block 0

I&M is a concept for uniform identification of field devices and is neither manufacturer nor industry-specific.
For this purpose, the field device provides particular information on an electronic product label.

Readout of block 0 of I&M functions (I&M0) is in line with PROFIBUS Identification & Maintenance Guideline
3502 and DPV2 encoder profile 3162. Data blocks I&M1 to I&M4 are not implemented.

I&M functions are accessed by Slot 0 or Slot 1 and index 255. Access to block I&M0 is by parameter number
65000 (0xFDE8).

Slot 0 of SIEMENS controls is addressed by the diagnosis address of the DP slave, in the example below
4093 (0x0FFD).

DS_WRITE

DP-V1 Header

Called parameter Value

Example

Function ID

Permanent for DS_Write

0x5F

ID

Slot 0 (diagnosis address DP-Slave)

0x0FFD

Index

255 = 0xFF

0xFF

User data length 4 = 0x04

0x04

Data Unit - Call Header (read):

Example

EXTENDED_

FUNCTION_NUM

0x08 permanent for CALL

0x08

reserved

ever 0x00

0x00

IM_INDEX (hi)

65000 = 0xFDE8

0xFD

IM_INDEX (lo)

65000 = 0xFDE8

0xE8

DS_READ

DP-V1 Header

Called parameter Value

Example

Function ID

Permanent for DS_Read

0x5E

ID

Slot 0 (Diagnose-Adresse DP-Slave)

0x0FFD

Index

255 = 0xFF

0xFF

Usere data length 68 = 0x44 max.

0x40

Data Unit - Call Header (read):

Example

EXTENDED_

FUNCTION_NUM

0x08 permanent for CALL

0x08

reserved

ever 0x00

0x00

IM_INDEX (hi)

65000 = 0xFDE8

0xFD

IM_INDEX (lo)

65000 = 0xFDE8

0xE8


Data Unit - Body (read):

Byte #

Example

0...9

Header

0x00

10

I&M Block

MANUFACTURER_ID

0x01

11

MANUFACTURER_ID

0x2A

12...31

ORDER_ID (20)

0x20

32...47

SERIAL_NUMBER (16)

0x20

48

HARDWARE_REVISION

0x00

49

HARDWARE_REVISION

0x00

50

SOFTWARE_REVISION (*4)

0x56 = ‘V’

51

SOFTWARE_REVISION

0x31 = ‘1’