beautypg.com

Profidrive parameter 965 profile number – Baumer GE-GB-GXxxx User Manual

Page 26

background image

Manual_ProfibusDPV2_BIDE_EN.docx

26/41

Baumer IVO GmbH & Co. KG

22.11.12

Villingen-Schwenningen, Germany

6.9.7. PROFIdrive parameter 965 profile number

Readout of the profile number. The encoder relates to the DPV2 encoder profile (PNO Order Nr 3.162),
version V3.2 of December 2004. For this reason the value replied is ever 0x03, 0x02.

DS_WRITE

DP-V1 Header

Called up

parameter

Value

Example

Function ID

Permanent for DS_Write

0x5F

ID

Slot no.1 (E/A address telegram81)

0x0200

Index

47 = 0x2F

0x2F

Length

8 = 0x08

0x08

Data Unit - (write):

Byte #

Example

0

Request Reference (example)

0xAA

1

Request ID=0x01 Change ID=0x02

0x01

2

Shaft no. (0=whole device)

0x00

3

Number of parameters

0x01

4

Attribute = “Value”

0x10

5

Number of parameter elements

0x01

6

Prm_no hi: 965 = 0x03C5

0x03

7

Prm_no lo: 965 = 0x03C5

0xC5


DS_READ

DP-V1 Header

Called parameter Value

Function ID

Permanent for DS_Read

0x5E

ID

Slot no.1 (E/A address telegram81)

0x0200

Index

47 = 0x2F

0x2F

Max.Length

64 = 0x40

0x40

Data Unit - (read):

Byte #

Example

0

Request Reference: mirrored

0xAA

1

Request ID

0x01

2

Shaft no. (0=whole device)

0x00

3

Number of parameters

0x01

4

Format: Unsigned16

0x06

5

Number of values

0x01

6

Profile number (hi)

0x03

7

Profile number (lo)

0x02