Manual_ProfibusDPV2_BIDE_EN.docx

10/41

Baumer IVO GmbH & Co. KG

22.11.12

Villingen-Schwenningen, Germany

Seal up the unused cable gland using a sealing bolt (included in the delivery).


1

2

3

Cable gland

M12 connector



Terminal assignment

M12 connector

Clamp:

Significance

M12, 4 pins: Pin 1

UB

Supply voltage 10...30 VDC

M12, 4 pins: Pin 3

GND

Ground connection related to UB

M12, 5 pins: Pin 2

A

Negative serial data line

M12, 5 pins: Pin 4

B

Positive serial data line


M12 connector
for serial data lines


for voltage supply

male

female


Clamps with the same designation are internally connected to each other and identical in function.
Maximum load on the internal clamped connections UB-UB and GND-GND is 1 A each.
Signals A and B are decoupled with an inductivity of 100 nH each.

Assembly of basic encoder and bus cover:

Carefully plug the bus cover onto the D-SUB connector of the basic encoder, then press it over the seal
taking care not to tilt it.

Tighten both fastening screws firmly in the same direction.

The bus cover must fully rest on the housing of the basic encoder and be firmly screwed on.



The encoder housing and braided shield of the connecting cable are only ideally connected if the bus cover is
resting fully on the basic encoder (positive locking).