Read / write spindle pitch (scaling) „c“ (63h), Read / write limit positions „g“ (67h) – Baumer N 152 User Manual

Page 20

background image

N 152

www.baumer.com

20

Holding torque
This parameter is utilized to enable respectively disable the motor holding torque. Both directional signals “motor
ccw” and “motor cw” are activated by the spindle position display (SPA). Thus, the motor is hold at its actual
position. Refer also to command „DB“ for temporary holding torque disabled.

0 = Off

holding torque disabled

1 = On

holding torque enabled


4.3.3. Read / write spindle tolerance compensation and window „b“ (62h)

This command is utilized to read or write the parameters tolerance compensation and tolerance window.

Example 1: Read parameter (tolerance compensation = 0.15; tolerance window = 0.25)

SOH

Adr

Cmd

EOT

CRC

Transmission

01h

20h

62h

04h

48h

SOH

Adr

Cmd

tolerance compensation=0.5

tolerance window=0.25

EOT

CRC

Response

01h

20h

62h

30h

30h

35h

30h

30h

30h

32h

35h

04h

0Bh


Example 2: Write parameter (tolerance compensation = 1.30; tolerance window = 0.75)

SOH

Adr

Cmd tolerance compensation =1.30

tolerance window =0.75

EOT

CRC

Transmission

01h

20h

62h

30h

31h

33h

30h

30h

30h

37h

35h

04h

1Eh

SOH

Adr

Cmd tolerance compensation =1.30

tolerance window =0.75

EOT

CRC

Response

01h

20h

62h

30h

31h

33h

30h

30h

30h

37h

35h

04h

1Eh


4.3.4. Read / write spindle pitch (scaling) „c“ (63h)

This command is utilized to read or write the scaling factor relating to the spindle pitch within the range from
0,0000001...9,9999999. The decimal point is not transmitted.
Resolution per turn is 1440 steps. A scaling factor of 1.000000 will increase respectively decrease the indicated
value by 14.4 mm.

How to calculate the scaling factor:
Resolution per turn: 14.40 mm (corresponding to length with scaling factor 1.0000000)
Spindle pitch:

4.00 mm

Spindle pitch 4.00
scaling = ───────────────── = ───── = 0.2777777

resolution per revolution 14.40

Example 1: Read scaling (scaling factor = 1.000000)

SOH

Adr

Cmd

EOT

CRC

Transmission

01h

20h

63h

04h

4Ah

SOH

Adr

Cmd

Scaling factor = 1.0000000

EOT

CRC

Response

01h

20h

63h

31h

30h

30h

30h

30h

30h

30h

30h

04h

4B


Example 2: Write scaling (scaling factor = 0.2777777)

SOH

Adr

Cmd

Scaling factor = 0.2777777

EOT

CRC

Transmission

01h

20h

63h

30h

32h

37h

37h

37h

37h

37h

37h

04h

30h

SOH

Adr

Cmd

Scaling factor = 0.2777777

EOT

CRC

Response

01h

20h

63h

30h

32h

37h

37h

37h

37h

37h

37h

04h

30h

4.3.5. Read / write limit positions „g“ (67h)

This command is utilized to read or write the MIN and MAX limit positions within the range from -999.99 to
9999.99. The decimal point is not transmitted.

Example 1: Read limit positions (MIN = 15.00; MAX = 850.25)

SOH Adr Cmd EOT CRC

Transmission

01h 20h 67h

04h 42h