Table 4 – Wet Coil Air Delivery
ENGLISH
400 VOLT
UNIT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
50JZ---A24
Low
Watts
303
305
306
300
---
---
---
---
---
---
---
Cfm
969
879
785
687
---
---
---
---
---
---
---
High
Watts
---
---
---
---
435
428
428
422
---
---
---
Cfm
---
---
---
---
963
833
758
676
---
---
---
50JZ---A30
Low
Watts
---
1002
954
921
889
853
814
---
---
---
---
Cfm
---
1189
1115
1041
971
903
833
---
---
---
---
High
Watts
---
---
---
---
---
---
---
700
683
688
755
Cfm
---
---
---
---
---
---
---
1223
1142
1075
1058
50JZ---A36
Low
Watts
552
540
529
523
514
480
---
---
---
---
---
Cfm
1296
1237
1167
1097
1029
952
---
---
---
---
---
High
Watts
---
---
---
---
---
782
765
736
721
780
1002
Cfm
---
---
---
---
---
1467
1398
1321
1237
1165
1137
50JZ---A48
Low
Watts
692
686
678
664
652
664
736
---
---
---
---
Cfm
1571
1509
1444
1370
1295
1240
1237
---
---
---
---
High
Watts
---
---
1112
930
856
834
825
811
793
---
---
Cfm
---
---
1693
1670
1601
1521
1447
1378
1294
---
---
SI
400 VOLT
UNIT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (Pa)
0
25
50
75
100
125
150
175
200
225
250
50JZ---A24
Low
Watts
303
305
303
300
---
---
---
---
---
---
---
L/s
458
415
371
324
---
---
---
---
---
---
---
High
Watts
---
---
---
---
435
428
428
422
---
---
---
L/s
---
---
---
---
455
393
358
319
---
---
---
50JZ---A30
Low
Watts
---
1002
954
921
889
853
814
---
---
---
---
L/s
---
561
526
491
458
426
393
---
---
---
---
High
Watts
---
---
---
---
---
---
---
700
683
688
755
L/s
---
---
---
---
---
---
---
577
539
508
499
50JZ---A36
Low
Watts
552
540
529
523
514
480
---
---
---
---
---
L/s
612
584
551
518
486
449
---
---
---
---
---
High
Watts
---
---
---
---
---
782
765
736
721
780
1002
L/s
---
---
---
---
---
693
660
624
584
550
536
50JZ---A48
Low
Watts
692
686
678
664
652
664
736
---
---
---
---
L/s
741
712
681
647
611
585
584
---
---
---
---
High
Watts
---
---
1112
930
856
834
825
811
793
---
---
L/s
---
---
799
788
756
718
683
650
611
---
---
*Air delivery values are based on operating voltage of 400---v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting.
NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh (165 L/s for each 3.5 kW) of rated cooling capacity. Evaporator
coil frosting may occur at airflow below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
Table 5 – Filter Pressure Drop (IN. W.C.) (Pa)
FILTER SIZE
in.
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
20X20X1
0.05
0.07
0.08
0.10
0.12
0.13
0.14
0.15
—
—
—
—
—
—
—
—
—
—
—
20X24X1
—
—
—
---
0.09
0.10
0.11
0.13
0.14
0.15
0.16
—
—
—
—
—
—
—
—
24X30X1
—
—
—
---
---
---
---
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
FILTER SIZE
mm
L/s
236
283
330
378
425
472
519
566
614
661
707
755
802
850
896
944
991
1038
1085
508X508X25
12.4
17.4
19.9
24.9
29.9
32.3
34.8
37.3
—
—
—
—
—
—
—
—
—
—
—
508X610x25
—
—
—
---
22.4
24.9
27.4
32.3
34.8
37.4
39.9
—
—
—
—
—
—
—
—
610X762x25
—
—
—
---
---
---
---
17.4
19.9
22.4
24.9
27.4
29.9
32.3
34.8
37.3
39.8
42.3
44.6
Table 6 – Accessory Electric Heat Pressure Drop IN. W.C. (Pa)
HEATER kW
CFM
600
800
1000
1200
1400
1600
1800
2000
2200
6.5--17.4
0.030
0.033
0.037
0.042
0.047
0.052
0.060
0.067
0.075
L/s
283
378
472
569
661
755
850
944
1038
7.5
8.2
9.2
10.4
11.7
12.9
14.9
16.7
18.7
50J
Z
--
A