F x 5 - s d t e c h n i c a l d ata F o r 5 0 h z
e l e c t r i c h e at e r s
C US
model
n
ote
a
ir Flow
v
oltage
n
ominal
W
attage
phase
m
ax.
m
otor
n
ameplate c
urrent
h
eater
W
attage
total
c
urrent
m
inimum circuit
a
mpacity
supply W
ire
m
aximum
Fuse
size
temperature
rise
c
ontactor
part
n
umber
(cFm) (v) (kW)
(W)
(a)
(a)
(aWg)
(a)
°c
°F
FX5-SD-220150-025
400
220
2.5
1
2.7
2270
11.4
14.3
14
15
11.0
19.8
3619
FX5-SD-220150-042
400
220
4.2
1
2.7
3950
19.1
23.9
10
25
18.4
33.2
3619
FX5-SD-220150-063
700
220
6.3
1
2.7
6050
28.6
35.8
8
40
15.8
28.5
3619
FX5-SD-220150-084
700
220
8.4
1
2.7
8140
38.2
47.8
6
50
21.1
37.9
3619
FX5-SD-220150-126 * 1450 220 12.6 1
1.4
12100 57.3
71.6
2
75
15.3
27.5
3619
FX5-SD-230150-028
400
230
2.8
1
2.7
2480
12.2
15.3
12
20
12.3
22.1
3619
FX5-SD-230150-046
400
230
4.6
1
2.7
4310
20.0
25.0
10
25
20.2
36.4
3619
FX5-SD-230150-069
700
230
6.9
1
2.7
6610
30.0
37.5
8
40
17.3
31.2
3619
FX5-SD-230150-138 * 1450 230 13.8 1
1.4
13200 59.9
74.9
2
80
16.7
30.1
3619
FX5-SD-380350-025
400
380
2.5
3
0.7
2270
3.8
4.8
16
5
11.0
19.8
3619
FX5-SD-380350-042
400
380
4.2
3
0.7
3950
6.4
8.0
16
10
18.4
33.2
3619
FX5-SD-380350-063
700
380
6.3
3
0.7
6050
9.6
12.0
14
15
15.8
28.5
3619
FX5-SD-380350-084
700
380
8.4
3
0.7
8140
12.8
16.0
12
20
21.1
37.9
3619
FX5-SD-380350-125
1450 380 12.5 3
0.7
12100 19.0
23.8
10
25
15.1
27.3
3619
FX5-SD-380350-209
3000 380 20.9 3
1.0
20300 31.8
39.8
8
40
12.2
22.0
3619
FX5-SD-400350-028
400
400
2.8
3
0.7
2480
4.0
5.0
16
5
12.3
22.1
3619
FX5-SD-400350-046
400
400
4.6
3
0.7
4310
6.6
8.3
16
10
20.2
36.4
3619
FX5-SD-400350-069
700
400
6.9
3
0.7
6610
10.0
12.5
14
15
17.3
31.2
3619
FX5-SD-400350-093
700
400
9.3
3
0.7
8900
13.4
16.8
12
20
23.3
42.0
3619
FX5-SD-400350-139
1450 400 13.9 3
0.7
13200 20.1
25.1
10
30
16.8
30.3
3619
FX5-SD-400350-185
1450 400 18.5 3
0.7
17800 26.7
33.4
8
35
22.4
40.3
3619
FX5-SD-400350-231
3000 400 23.1 3
1.0
22200 33.3
41.6
8
45
13.5
24.3
3619
FX5-SD-415350-037
400
415
3.7
3
0.7
3510
5.1
6.4
16
10
16.3
29.3
3619
FX5-SD-415350-075
700
415
7.5
3
0.7
7240
10.4
13.0
14
15
18.8
33.9
3619
FX5-SD-415350-149
1450 415 14.9 3
0.7
14500 20.7
25.9
10
30
18.1
32.5
3619
FX5-SD-415350-224
3000 415 22.4 3
1.0
21800 31.2
39.0
8
40
13.1
23.6
3619
FX5-SD-440350-042
400
440
4.2
3
0.7
3950
5.5
6.9
16
10
18.4
33.2
3619
FX5-SD-440350-084
700
440
8.4
3
0.7
8140
11.0
13.8
14
15
21.1
37.9
3619
FX5-SD-440350-168
1450 440 16.8 3
0.7
16300 27.5
34.4
8
35
20.4
36.6
3619
FX5-SD-440350-210
3000 440 21.0 3
1.0
20300 27.5
34.4
8
35
12.3
22.1
3619
notes:
* Exceeds the 48 Amp Circuit Limit of NEC 424-22. DS5 not available for these units.
1. Minimum conductor size for 30˚C (86˚F) ambient. Derate conductor for ambient temperature. Use minimum 90˚C (194˚F) insulation.
2. Heater is functioning normally if at rated voltage the amp draw is within 10% of the value in this table.
3. Operation at lower voltages will result in reduced heat output and amp draw
4. Add "T" to model number when adding a built-in thermostat
5. Add "D" to model number when adding a built-in disconnect switch
6. Add "U" to model number for units with continuous fan option.
7. Add "A" to model number for units with stainless steel cabinet.