CCI Thermal Technologies XTD8 - Explosion-Proof Thermostat (Room) User Manual
CCI Thermal Technologies Water boiler

CCI Thermal Technologies
5918 Roper Road
Edmonton, AB T6B 3E1
(800) 661-8529
www.ccithermal.com
INSTALLATION INSTRUCTIONS FOR EXPLOSION-PROOF
THERMOSTATS
XTD8-S SPDT Heat/Cool
Approved for
the following
Hazardous location
designations:
Divisions 1 & 2
Class I, Groups C & D
Class II, Groups E, F, & G
APPLICATION:
For use in locations where flammable and explosive mixtures of vapors, gas or combustible dust in
the air, are present.
Temperature setting range is 5ºC to 25ºC (40ºF to 80ºF) heating or cooling.
ELECTRICAL RATINGS:
22 Amp 125-277 VAC
3/4 HP @ 125 VAC; 1-1/2 @ 250/277 VAC
LOCATION:
Locate the thermostat approximately five feet (5’) above the floor in a location that will sense the aver-
age temperature of the are to be controlled. Do not mount the thermostat adjacent to water pipes,
in drafty areas, or other locations that would adversely affect the operation of the thermostat. If the
thermostat is mounted on an exterior wall that in not insulated, an insulating pad should be placed
between the thermostat and the exterior wall.
TM
TM