APPENDIX 1: INPUT WIRING REQUIREMENTS

NOTES

Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.

Cable size is de-rated based on the Duty Cycle of the equipment.

The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.

Cable conductor temperature used is 167° F (75° C).

An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.

NEVER

use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.

In p u t

P o w er In p u t

C u r r e n t

S u g g e st ed S iz es ( S ee N o t e)

V o lt ag e

F r eq .

3- P h

3- P h

F u s e ( A m p s )

W ir e ( A W G )

W ir e ( C a n ad a )

( V o lt s)

( H z )

( kV A )

( A m p s )

3- P h

3- P h

3- P h

20 0

50 /60

34

98

11 0

A W G 2

2

20 8

50 /60

34

95

11 0

A W G 2

2

22 0

50 /60

34

89

10 0

A W G 2

2

23 0

50 /60

34

85

10 0

A W G 4

2

38 0

50 /60

34

51

60

A W G 6

6

41 5

50 /60

34

47

60

A W G 8

6

46 0

50 /60

34

42

50

A W G 8

6

50 6

50 /60

34

40

45

A W G 8

6

57 5

50 /60

34

34

40

A W G 8

6

Li ne V o l ta ges w i th S ugg es ted C i r c ui t P r ote c ti on and W i r e S i z es

B as ed on N a ti o nal E l ec tr i c C o de and C an adi an E l ec tr i c a l C od e