CHAMPION SL20 PUMP OPERATION / MAINTENANCE MANUAL

PAGE 9

The PLC display is show in Figure 3-22. Please note the names of the different
areas of the PLC display.

Figure 3-22:

3.1.a The PLC outputs are shown in Table 2.

• Relay output 500 is a “fail safe”, normally open relay. It is equipped with

a 15 second delay, intended to identify pump operation.

• Relay 500 will disengage, (turn “OFF”) if the PLC does not recognize

alternating condition of the EOS inputs within the 15 seconds.

• The pump will require manual engagement by turning relay 17901

“ON” (see section 3.1.b).

• During initial start-up relay 500 will be “ON” or in the closed position (~15

seconds) while verification for EOS probe alternation is performed.

RLY

Output

Description

Default

Value

500

Pump Operating - Normally open output

OFF

Table 2: Customer PLC Output

3.1.b Changing a pump function listed in Table 3:

RLY

Description

Default

Value

17901

Pump On – Turns pump on and off

On

17902

Auto Tune Mode – Enables the auto tuning feature of the
controller
Non manual setup requiring EOS probes.

On

17903

Reset Auto Tune – Forces the controller to run an auto tune cycle

Off

17904

Booster Mode – Enables booster mode disabling vacuum fill.

Off

17905

Reset PM – Resets the pump maintenance cycle count

Off

17906 N/A

Off

17907

Reset to defaults – resets all data memories to default values

Off

Table 3: PLC Internal Relays