Adjus t menu – tekmar 420 Boiler Reset Module User Manual
Page 9
9 of 24
© 2007
D 420 - 08/07
Item Field
Range
Access
Description
100 to 220°F
(38.0 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
DHW EXCHANGE OCCUPIED
SECTION F
The minimum boiler target temperature to the DHW
heat exchanger during the Occupied period.
Note:
This item is only available when DHW Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
DHW EXCHANGE UNOCCUPIED
SECTION F
Selects whether the control should respond to DHW
demands during the Unoccupied period. This item is
only available when DHW Mode is set 1 through 4
and a network setback schedule is selected.
OFF,
1 (parallel, no priority)
2 (parallel, priority)
3 (pri-sec, no priority)
4 (Pri-sec, priority)
Default = 1
Ad
SETPOINT MODE
SECTION H
Selects the Setpoint mode of operation. This
determines the operation of the primary pump.
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
SETPOINT OCCUPIED
SECTION H
The minimum boiler target temperature when a
setpoint demand is present during the Occupied
period.
Note:
This item is only available when Setpoint Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
SETPOINT UNOCCUPIED
SECTION H
Selects whether or not a Setpoint demand will be
responded to during the UnOccupied period.
Note:
This item is only available when Setpoint Mode
is set 1 through 4 and a network setback schedule
is selected.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 70°F (21.0°C)
InS
Ad
WWSD OCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
Ad
WWSD UNOCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note:
This item is only available when the Schedule
is not set to OFF.
Adjust Menu (3 of 3)
ADJUS
T MENU
After the last item, the control returns to the first item in the menu.