DHW with Low Temperature Boilers
Section G
If DHW heating is to be incorporated into a low temperature 
system such as a radiant floor heating system, a mixing 
device is often installed to isolate the high DHW supply 
temperature from the lower system temperature. If a mixing 
device is not installed, high temperature water could be 
supplied to the low temperature system while trying to 
satisfy the DHW demand. This may result in damage to 
the low temperature heating system.
The control is capable of providing DHW heating in such a 
system while minimizing the chance that the temperature 
in the heating system exceeds the design supply water 
temperature. In order to do this, the control must be set 
to DHW MODE 2 or DHW MODE 4 and Boil MIN must be 
set to OFF.
On a call for DHW, the control provides DHW priority by 
sending a message on the boiler temperature bus to the tN4 
thermostats to shut off the heating zones for a period of time. 
The length of time is based on the outdoor air temperature as 
described in the DHW Priority Override section. However, if 
the DHW Demand is not satisfied within the allotted time, the 
boiler shuts off and the heat of the boiler is purged into the 
DHW tank. A DHW mixing purge occurs in order to reduce 
the boiler water temperature and once the boiler supply 
temperature is sufficiently reduced, the DHW Pump contact 
shuts off. The heating system zones are allowed to turn on 
for a period of time to prevent the building from cooling off. 
After a period of heating, and if the DHW Demand is still 
present, the control shuts off the heating system and provides 
heat to the DHW tank once again.
Setpoint Temperature Operation
Section H
Setpoint
The control can operate to satisfy the requirements of a 
setpoint load in addition to a space heating load and a 
DHW load. A setpoint load overrides the current outdoor 
reset temperature and WWSD setting in order to provide 
heat to the setpoint load.
Setpoint Demand
A Setpoint Demand is required in order for the control to 
provide heat to a setpoint load.
The control registers a setpoint demand when a voltage 
between 24 and 230 V (ac) is applied across the Setpoint 
Demand terminals (55 and 56). Once voltage is applied, 
the Setpoint Demand segment turns on in the LCD.
Boiler Target During Setpoint
The boiler target temperature during a Setpoint Demand is 
increased to at least the Setpoint setting. This temperature 
is maintained as long as the control has a setpoint 
demand.
Setpoint During UnOccupied
The control has a Setpoint UnOccupied setting that allows 
the installer to select On or Off. When set to On, and the 
control receives a Setpoint Demand during an UnOccupied 
or Sleep period, the control continues operation of the 
Setpoint system as it would during Occupied and Wake 
periods. When set to Off, the control can ignore a Setpoint 
Demand for the duration of the UnOccupied and Sleep 
periods.
Setpoint Modes
The Setpoint Mode determines the operation of the 
primary pump. The Setpoint Mode setting is found in the 
Adjust menu.
Setpoint Mode 1 - Setpoint in Parallel
Whenever a setpoint demand is present, the boiler is 
operated to maintain the setpoint target. The primary pump 
(P1) does not turn on, but may operate based on either a 
Boiler, Mixing or a DHW Demand.
It is assumed that the Setpoint pump will provide adequate 
flow through the heat exchanger and the boiler.
Primary
Pump
Setpoint
Mode = 1
Setpoint Mode 2 - Setpoint in Parallel with Priority
When a Setpoint Demand is present, the boiler is operated 
to maintain the setpoint target. The primary pump (P1) 
can operate when a boiler demand is present. If the 
boiler is unable to maintain the boiler target temperature, 
space heating zones are shut off sequentially using tN4 
communication in order to provide priority for the setpoint 
load. This is known as zone load shedding.
It is assumed that the setpoint pump will provide adequate 
flow through the heat exchanger and the boiler.
Setpoint
Primary
Pump
OFF
Mode = 2