Adjus t menu – tekmar 420 Boiler Reset Module User Manual

Page 7

background image

7 of 24

© 2007

D 420 - 08/07

Item Field

Range

Access

Description

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

InS

Ad

OUTDOOR DESIGN

SECTION B

The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically set
to the temperature of the coldest day of the year.

1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 4

InS

Ad

BOILER TERMINAL

SECTION B

The type of heating terminal units that are being
used in boiler zones.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F

(21.0°C)

Ad

BOILER INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for the boiler zones. Typically set to
70°F (21.0°C).

70 to 220°F

(21.0 to 104.5°C)

Default = 180°F

(82.0°C)

InS

Ad

BOILER DESIGN

SECTION B

The supply water temperature required for boiler
zones on the typical coldest day of the year.

OFF, 80 to 180°F

(OFF, 26.5 to 82.0°C)

Default = 140°F

(60.0°C)

InS

Ad

BOILER MINIMUM

SECTION C

The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.

120 to 225°F, OFF

(49.0 to 107.0°C, OFF)

Default = 200°F

(93.5°C)

Ad

BOILER MAXIMUM

SECTION C

The maximum allowed boiler target temperature.

0:00 to 3:00 min

Default = 0:10 min

Ad

FIRE DELAY

SECTION C

The time delay the control can expect between the
time that the relay contact closes to fire the boiler
and when the burner actually fires.

Adjust Menu (1 of 3)

The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.

Continued on next page.

ADJUS