Adjus t menu – tekmar 420 Boiler Reset Module User Manual
Page 7
7 of 24
© 2007
D 420 - 08/07
Item Field
Range
Access
Description
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
InS
Ad
OUTDOOR DESIGN
SECTION B
The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically set
to the temperature of the coldest day of the year.
1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 4
InS
Ad
BOILER TERMINAL
SECTION B
The type of heating terminal units that are being
used in boiler zones.
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F
(21.0°C)
Ad
BOILER INDOOR
SECTION B
The design indoor air temperature used in the heat
loss calculation for the boiler zones. Typically set to
70°F (21.0°C).
70 to 220°F
(21.0 to 104.5°C)
Default = 180°F
(82.0°C)
InS
Ad
BOILER DESIGN
SECTION B
The supply water temperature required for boiler
zones on the typical coldest day of the year.
OFF, 80 to 180°F
(OFF, 26.5 to 82.0°C)
Default = 140°F
(60.0°C)
InS
Ad
BOILER MINIMUM
SECTION C
The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.
120 to 225°F, OFF
(49.0 to 107.0°C, OFF)
Default = 200°F
(93.5°C)
Ad
BOILER MAXIMUM
SECTION C
The maximum allowed boiler target temperature.
0:00 to 3:00 min
Default = 0:10 min
Ad
FIRE DELAY
SECTION C
The time delay the control can expect between the
time that the relay contact closes to fire the boiler
and when the burner actually fires.
Adjust Menu (1 of 3)
The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.
Continued on next page.
ADJUS
T MENU