Boiler maximum, Fire delay, On-off boiler operation – tekmar 420 Boiler Reset Module User Manual
Page 15: Modulating boiler operation

15 of 24
© 2007
D 420 - 08/07
Boiler Maximum
The boiler maximum is the highest temperature that the 
control is allowed to use as a boiler target temperature. If 
the control does target the Boiler Maximum setting, and the 
boiler temperature is near the boiler maximum temperature, 
the maximum segment will be displayed in the LCD while 
either the boiler target temperature or the boiler temperature 
is being viewed. At no time does the control operate the 
boiler above 248°F (120.0°C).
•
• Locate the Boiler Maximum setting in the Adjust menu.
B
oil Wa
te
r T
em
peratur
e
B
oil Wa
te
r T
em
peratur
e
Boil MIN + 1/2 Boiler Differential
Boil MAX
Boil MIN – 1/2 Boiler Differential
MAX
segment
on
MAX
segment
on
Fire Delay
The Fire Delay is the time delay that occurs between the 
time that the control closes the boiler contact to fire the 
boiler and when the burner fires.
•
• Locate the Fire Delay setting in the Adjust menu.
Boiler Contact Closed
Time
Fire Delay
Burner On
On-Off Boiler Operation
If the heat source is an On-Off Boiler, the Boil On-Off / Mod 
DIP switch must be set to On-Off.
Differential
An on / off heat source must be operated with a differential 
in order to prevent short cycling. With the control, either 
a fixed or an auto differential may be selected. The boiler 
differential is divided around the boiler target temperature. 
The boiler contact closes when the supply water temperature 
is 1/2 of the differential setting below the boiler target 
temperature. As the supply temperature reaches 1/2 of 
the differential above the boiler target temperature, the 
boiler is shut off.
•
• Locate the Boiler Differential setting in the Adjust menu.
Differential = 10°F (6°C)
Target + 1/2 Differential
Target – 1/2 Differential
Target
165°F (74°C)
160°F (71°C)
155°F (68°C)
Boiler
On
Boiler
On
Fixed Differential
If the user desires to have a fixed differential, this is set 
using the Boiler Differential setting in the Adjust menu.
Auto Differential
In order to decrease temperature swings and increase boiler 
efficiency, the Auto Differential feature automatically changes 
the on / off differential of the boiler based on the heating 
load. As the load increases, the differential will decrease to 
minimize temperature swings. As the load decreases, the 
differential will increase to prevent short cycling.
Off
Differential
Time
Heating Load
On
Modulating Boiler Operation
The 420 can operate a single hot-water modulating boiler. 
This requires the use of the Mod (dc) output on the 420.
To operate a modulating boiler, the Boil On-Off / Mod DIP 
switch must be set to Mod. The control operates the boiler 
by first switching the boiler contact to allow the modulating 
boiler to go through the ignition sequence (the boiler contact 
may not be required on all modulating boilers). A 0-10 V (dc) 
analog signal is used to modulate the boiler firing rate 
from the Minimum Modulation setting using Proportional, 
Integral and Derivative (PID) logic in order to satisfy the 
boiler target temperature.
A modulating boiler requires all the same settings as an 
on-off boiler in addition to the settings below.
Modulating Boiler Differential
A modulating boiler must be operated with a differential 
while operating in low fire. The boiler differential is divided 
around the boiler target temperature. The boiler burner 
ignites at low fire when the supply water temperature is 
1/2 of the Boiler Differential setting below the boiler target 
temperature. The boiler is shut off in low fire as the supply 
temperature reaches at least 1/2 of the differential above 
the boiler target temperature. With the control, either a fixed 
or an auto differential may be selected.
When the boiler is modulating above low fire, the differential 
does not apply. Instead, the modulation output signal is 
determined using Proportional, Integral and Derivative (PID) 
logic in order to satisfy the boiler target temperature.
