beautypg.com

Sequence of operation, Tekmarnet – tekmar 420 Boiler Reset Module User Manual

Page 12

background image

© 2007

D 420 - 08/07

12 of 24

tekmarNet

®

4 Communication

Section A

tekmarNet

®

4 (tN4) communicates between tN4 devices

(thermostats, Reset Module and Expansion Modules). Each
tN4 device is connected to a tN4 communication bus using
two wires. Each tN4 bus adjusts a single water temperature
in the system using indoor temperature feedback. The Boiler
Reset Module 420 allows for one tN4 bus. This allows you
to control a system with one water temperature.

A system that has more than one tN4 bus is referred to as
a tN4 network.

Outdoor Reset Module

The Boiler Reset Module 420 is the system control for a
hydronic heating system. The 420 operates a single heat
source such as a boiler, a domestic hot water tank, and
responds to other heating requirements such as pool heating
and snow melting. The 420 also coordinates and optimizes
the operation of all the tN4 thermostats.

tN4 Thermostat

The tN4 thermostat operates heating, cooling, and or
ventilation equipment for a zone. Several tN4 thermostats
may work in a group when operating a cooling system. Up
to 24 tN4 thermostats can connect to a single tN4 bus.

Outdoor Reset

Section B

In a heating system, the rate of heat supplied to the building
must equal the rate of which heat is lost. If the two rates are
not equal, the building will either cool off or over heat.

The rate of building heat loss depends mostly on the outdoor
temperature. Outdoor Reset allows a hot water heating
system to increase the water temperature, adding heat to
the building, as the outdoor temperature drops. The rate
at which the water temperature is changed is defined by
the characterized heating curve.

Characterized Heating Curves

A characterized heating curve determines the amount the
supply water temperature is raised for every 1° drop in
outdoor air temperature. There is a characterized heating
curve for each tN4 communication bus.

The characterized heating curve takes into account the
type of terminal unit that the system is using. Since different
types of heating terminal units transfer heat to a space using

different proportions of radiation, convection and conduction,
the supply water temperature must be controlled differently.
Each tN4 bus is assigned a terminal unit setting that the
control uses to vary the supply water temperature to suit
to the terminal unit used. This improves the control of the
air temperature in the building.

Indoor Temperature Feedback

Most buildings have internal heat gains due to people,
passive solar heating and mechanical or electrical equipment.
Likewise, wind loads cause a building to lose heat faster than
during design conditions. If only the outdoor temperature is
measured, the control cannot compensate for these internal
heat gains or loses and the building may over or under heat.
In order to maintain the most comfortable temperature,
the control uses indoor temperature feedback from tN4
thermostats in order to adjust the water temperature on
each tN4 bus on a continual basis.

Sequence of Operation

Zone A1

Zone A2

Power

Zone Group Pump A

Zone A3

Zone B1

Zone B2

Zone B3

tN4

Zone Group Pump B

Bus 1

Bus 2

Network

tekmarNet

®

4

Thermostats

tekmarNet

®

4

Thermostats

tN4

Test

Item

Menu

Do not apply power

Test

Wait

3

seconds

Test

Hold
for 6

seconds