Sequence of operation, Tekmarnet – tekmar 420 Boiler Reset Module User Manual
Page 12

© 2007
D 420 - 08/07
12 of 24
tekmarNet
®
4 Communication
Section A
tekmarNet
®
4 (tN4) communicates between tN4 devices
(thermostats, Reset Module and Expansion Modules). Each 
tN4 device is connected to a tN4 communication bus using 
two wires. Each tN4 bus adjusts a single water temperature 
in the system using indoor temperature feedback. The Boiler 
Reset Module 420 allows for one tN4 bus. This allows you 
to control a system with one water temperature.
A system that has more than one tN4 bus is referred to as 
a tN4 network.
Outdoor Reset Module
The Boiler Reset Module 420 is the system control for a 
hydronic heating system. The 420 operates a single heat 
source such as a boiler, a domestic hot water tank, and 
responds to other heating requirements such as pool heating 
and snow melting. The 420 also coordinates and optimizes 
the operation of all the tN4 thermostats.
tN4 Thermostat
The tN4 thermostat operates heating, cooling, and or 
ventilation equipment for a zone. Several tN4 thermostats 
may work in a group when operating a cooling system. Up 
to 24 tN4 thermostats can connect to a single tN4 bus.
Outdoor Reset
Section B
In a heating system, the rate of heat supplied to the building 
must equal the rate of which heat is lost. If the two rates are 
not equal, the building will either cool off or over heat.
The rate of building heat loss depends mostly on the outdoor 
temperature. Outdoor Reset allows a hot water heating 
system to increase the water temperature, adding heat to 
the building, as the outdoor temperature drops. The rate 
at which the water temperature is changed is defined by 
the characterized heating curve.
Characterized Heating Curves
A characterized heating curve determines the amount the 
supply water temperature is raised for every 1° drop in 
outdoor air temperature. There is a characterized heating 
curve for each tN4 communication bus.
The characterized heating curve takes into account the 
type of terminal unit that the system is using. Since different 
types of heating terminal units transfer heat to a space using 
different proportions of radiation, convection and conduction, 
the supply water temperature must be controlled differently. 
Each tN4 bus is assigned a terminal unit setting that the 
control uses to vary the supply water temperature to suit 
to the terminal unit used. This improves the control of the 
air temperature in the building.
Indoor Temperature Feedback
Most buildings have internal heat gains due to people, 
passive solar heating and mechanical or electrical equipment. 
Likewise, wind loads cause a building to lose heat faster than 
during design conditions. If only the outdoor temperature is 
measured, the control cannot compensate for these internal 
heat gains or loses and the building may over or under heat. 
In order to maintain the most comfortable temperature, 
the control uses indoor temperature feedback from tN4 
thermostats in order to adjust the water temperature on 
each tN4 bus on a continual basis.
Sequence of Operation
Zone A1
Zone A2
Power
Zone Group Pump A
Zone A3
Zone B1
Zone B2
Zone B3
tN4
Zone Group Pump B
Bus 1
Bus 2
Network
tekmarNet
®
4
Thermostats
tekmarNet
®
4
Thermostats
tN4
Test
Item
Menu
Do not apply power
Test
Wait
3
seconds
Test
Hold
for 6
seconds
