tekmar 512 Programmable Thermostat Installation User Manual

Page 9

background image

9 of 20

© 2009

D 512 - 09/09

Adjust Menu (3 of 4)

SLAB MAXIMUM

Maximum slab temperature. This item is only available in the
Installer access level. (Must have an active slab sensor.)

34 to 122°F, OFF (1.0 to 50.0°C, OFF)

SENSOR 1

Selects the type of auxiliary sensor present in the Sen 1 input. This
item is only available in the Installer access level.

OFF, Indr, SLAB, REM

SENSOR 2

Selects the type of auxiliary sensor present in the Sen 2 input. This
item is only available in the Installer access level.

OFF, Indr, SLAB, OUT

ROOM SENSOR

Selects whether the built-in sensor is functional or not. This item
is only available in the Installer access level.

OFF, ON

HEATING CYCLE

Determines the number of cycles per hour for the heating
equipment. This item is only available in the Installer access level.

Auto, 2 to 12

COOLING CYCLE

Determines the number of cycles per hour for the cooling equipment.
This item is only available in the Installer access level.

Auto, 2 to 12

COOLING INTERLOCK

Selects the time delay between the heating and cooling relays. This
item is only available in the Installer access level.

10 to 180 min.

COOLING MINIMUM ON

Sets the minimum on time of the cooling contact. This is to prevent
short cycling. This item is only available in the Installer access level.

0:30 to 5:00 min.