Item Field

Range

Description

VIEW

Zones

Calls

Pumps

-76 to 149°F

(-60.0 to 65.0°C)

OUTDOOR

SECTION B, C

Current outdoor air temperature as measured by the outdoor sensor. The
outdoor air temperature is shared to all thermostats in the tekmarNet

®

system.

VIEW

Zones

Calls

Pumps

-22 to 266°F

(-30.0 to 130.0°C)

MIX SUPPLY

SECTION B

Current mix supply water temperature as measured by the mix supply
sensor. The control operates the mixing device so that the mix supply
is equal to the mix target temperature.

VIEW

Zones

Calls

Pumps

– – –, 35 to 180°F

(1.5 to 82.0°C)

MIX TARGET

SECTION B

The temperature the control is currently trying to maintain at the mix
supply sensor. The mix target is calculated based on the outdoor
design and mix design settings. “– – –” is displayed when no heat is
required for mix zones.

VIEW

Zones

Calls

Pumps

-22 to 266°F

(-30.0 to 130.0°C)

BOILER SUPPLY

SECTION C

Current boiler supply water temperature as measured by the boiler
sensor. The control operates the boiler so that the boiler supply is
within the boiler differential of the boiler target. ‘MIN’ is shown when
the control is providing boiler minimum protection to the boiler.

VIEW

Zones

Calls

Pumps

– – –, 35 to 200°F

(1.5 to 93.0°C)

BOILER TARGET

SECTION C

The boiler target is the temperature the control is currently trying to
maintain at the boiler supply sensor. The boiler target is calculated based
on the outdoor design, boiler design, and boiler minimum settings. “– – –”
is displayed when no heat is required. ‘MIN’ is shown when the control
is providing boiler minimum protection to the boiler.

VIEW

Zones

Calls

Pumps

0-100%

BOILER MODULATION

SECTION F

Current percent modulation of the boiler’s burner. The boiler modulation
increases when the boiler supply is less than the boiler target. The
boiler modulation decreases when the boiler supply is greater than the
boiler target.
Note: This item is only available when the Boil Type setting is set to
0-10 or 4-20.

-22 to 266°F

(-30.0 to 130.0°C)

DHW TANK

SECTION D

Current Domestic Hot Water tank temperature as measured by the optional
DHW sensor. If the DHW tank temperature falls 6°F (3.0°C) below the
DHW Occ setting, a DHW call is created and the tank is heated.
Note: This item is only available when a DHW sensor is installed and
DHW Mode is set to 1 to 4.

-22 to 266°F

(-30.0 to 130.0°C)

DHW SUPPLY

SECTION D

Current supply water temperature to the indirect DHW tank heat
exchanger as measured by the DHW sensor.
Note: This item is only available when a DHW sensor is installed and
DHW Mode is set to 5.

--

SYSTEM IN AWAY

SECTION I

The heating system is in the Away scene. The DHW tank will not be
heated. Setpoint calls are still responded to.
Use the User Switch to change scene out of Away.

VI

EW

M

E

N

U

View Menu (1 of 1)

The View menu items display the current operating temperatures and status information
of the system.

After the last item, the control returns to the first item in the menu.