Adjust Menu (1 of 2)
The type of terminal units that are being used in the
heating system.
(OUTDR DSGN
≠
OFF)
1 (High Mass Radi-
ant), 2 (Low Mass
Radiant), 3 (Fancoil),
4 (Fin-tube Convec-
tor), 5 (Radiator),
6 (Baseboard)
B2
The desired room air temperature during an
occupied (Day) period.
(OUTDR DSGN
≠
OFF)
35 to 100
°F
(2 to 38
°C)
B2
The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN
≠
OFF)
35 to 100
°F
(2 to 38
°C)
B2
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
60 to 200
°F
(16 to 93
°C)
The design outdoor air temperature used in the
heat loss calculation for the heating system. For
setpoint operation, set the OUTDR DSGN to OFF.
-60 to 32
°F, OFF
(-51 to 0
°C, OFF)
Display
Description
Range
The design supply water temperature used in the
heat loss calculation for the heating system.
(OUTDR DSGN
≠
OFF)
70
°F to 220°F
(21 to 104
°C)
B3
The design indoor air temperature used in the heat
loss calculation for the heating system.
(OUTDR DSGN
≠
OFF)
35 to 100
°F
(2 to 38
°C)
B3
The maximum supply temperature for the mixing
system.
(OUTDR DSGN
≠
OFF)
80 to 210
°F
(27 to 99
°C)
B3
The minimum supply temperature for the mixing
system.
(OUTDR DSGN
≠
OFF)
OFF, 35 to 150
°F
(OFF, 2 to 65
°C)
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 80 to 180
°F
(OFF, 27 to 82
°C)
C1
The differential that the control is to use when it is
operating the boiler.
(
Boiler Sensor DIP switch = Supply AND Boiler
sensor is present)
Ad, 2 to 42
°F
(Ad, -17 to 6
°C)
C2
B3
B2
B2
Section
Advanced
Installer
Actual
Setting
ADJUST
INDR
MIX
°
F
ADJUST
DSGN
MIX
°
F
ADJUST
MIX
°
F
MAX
ADJUST
BOIL
°
F
MIN
ADJUST
DIFF
BOIL
ADJUST
ROOM
°
F
OCC
UN
ADJUST
Terminal Unit
ADJUST
DSGN
OUTDR
°
F
ADJUST
ROOM
°F
OCC
ADJUST
MIX MIN
ADJUST
TARGET
MIX
°F