beautypg.com

Field test, Error messages, Item – tekmar 257 DHW Control User Manual

Page 11

background image

11 of 12

© 2009 D 257 - 03/09

Field Test

To test the control, push and hold the up button for 3
seconds while in the default menu. While in Field Test
“tSt” is displayed.

Step 1: Heat 1 relay will close and Heat 2 relay will open

for 10 seconds

Step 2: If rotate switch is off, both Heat 1 and Heat 2 relays

will close for 10 seconds. If rotate switch is on, Heat
1 relay will open and Heat 2 relay will close for 10
seconds.

Step 3: The test routine ends and the control resumes normal

operation.

Item

Stage Mode

Delay

Target DHW

Differential

DHW

Error Messages

Stage Mode

Delay

Target DHW

Differential

DHW

EEPROM READ ERROR
The control was unable to read a piece of information stored in it’s memory. Because
of this, the control was required to reload factory settings for all items in the PRGM
menu. The control will stop operation until all of the items in the PRGM menu have
been checked.

Stage Mode

Delay

Target DHW

Differential

DHW

DHW SENSOR ERROR
The control is no longer able to read the DHW Sensor due to an open or short circuit.
Locate and repair the problem as described in the Data Brochure D 070. The outputs
will not operate until the error is cleared.