9.2.7 High temperature protection of compressor top diagnosis and solution(P2)

Check if the air flow system

of indoor and outdoor units

are obstructed?

Clear up the air inlet and outlet or the heat

exchanger of indoor and outdoor units.

Yes

No

Yes

Yes

Turn off the power supply and turn
it on 10 minutes later.

Check if the unit can

start normally.

No

Check if the refrigerant

charge volume is normal?

Recharge the correct

refrigerant volume.

Refrigerant system is blocked, such

as capillary or welded point of pipes.

Yes

Check if all the connection, especially

the connection of OLP (Over Load

Protector) sensor is good.

Correct the connection.

No

Measure the resistance
between the two ports of
the OLP. Is it zero?

Yes

Replace the OLP.

No

Replace the outdoor control PCB.

Yes

No