9.2.6 Over voltage or too low voltage protection diagnosis and solution(P1)

Check if the power supply is

normal.

Check if all the connections
and wires are good?

Disconnect the unit with power

supply and try to restart the unit

when power supply gets normal.

No

Yes

No

Correct the connections or replace

the wires.

Yes

Power on and when the unit is in

standby, check if the voltage

between P and N is around DC

310V or 340V or 380V? For different

kinds of units, the voltage differs.

Consult with technical engineer to

get definite value. Then start up the

unit, measure the voltage between

P and N. Is it in 220V~400V?

Replace outdoor mainl PCB.

Yes

No

Replace the IPM board if it is separate

with main PCB.