Hold: Keep the current frequency.

Resume: No limitation for frequency.

Note:

When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level. (The

frequency will increase twice at most)

8.4.3.2 Outdoor fan running rules

17

15

Low

High

8.4.3.3 Indoor fan running rules

TEL8

TEL7

TEL6

TEL5

T2

TEL4

Setting

Low

Breeze

Off

TEL3

Medium

TEL2

TEL0

Super

Breeze

TEL1

If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127

seconds with breeze. During this period, the anti-cold-wind is disabled.

If the machine runs in rating capacity test mode, the indoor fan will run with rating speed and the

anti-cold-wind function is disabled.