Klimaire KSIN Series Service Manual User Manual
Page 42
40
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level. (The
frequency will increase twice at most)
8.4.3.2 Outdoor fan running rules
17
15
Low
High
8.4.3.3 Indoor fan running rules
TEL8
TEL7
TEL6
TEL5
T2
TEL4
Setting
Low
Breeze
Off
TEL3
Medium
TEL2
TEL0
Super
Breeze
TEL1
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
If the machine runs in rating capacity test mode, the indoor fan will run with rating speed and the
anti-cold-wind function is disabled.