Klimaire KSIN Series Service Manual User Manual

Page 38

background image

36

F: Keep the current frequency.

G: Decrease the frequency to the lower level until to F1.

H: Run at F1 for 1h.(if T1-Ts<-2℃, the compressor will stop)

Meanwhile, the compressor running frequency is limited by the current.

I3COOL

I2COOL

Off

Decrease

Hold

Resume

I1COOL

Off: Compressor stops.

Decrease: Decrease the running frequency to the lower level.

Hold: Keep the current frequency.

Resume: No limitation for frequency.

Note:

When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher

level.(frequency will increase twice at most)

8.4.2.2 Outdoor fan running rules

22

20

High

Low

8.4.2.3 Indoor fan running rules

In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and

auto.

Auto fan in cooling mode acts as follow: