beautypg.com

Klimaire KSIN Series Service Manual User Manual

Page 52

background image

50

9.2.2 Indoor / outdoor unit’s communication error diagnosis and solution(E1)

Yes

Yes

Measure Vs, is it moving alternately
between positive value and negative
value?
(Vs is the voltage between S and N of
outdoor unit.)

Yes

Power off, then turn on the unit 5 seconds
later(reconnect the power wire ).Is the error
still displaying after several minutes?

No

Yes

Change the outdoor main PCB.

Power on. Is the error extinguished?

Check all the wirings between indoor and
outdoor, indoor main PCB and outdoor main
PCB following the wiring diagram. Are all
the wirings connected correctly?

Is the wiring to the indoor main
PCB connected correctly?

Change the indoor main PCB.

Yes

Change the outdoor main PCB.

No

Is the wiring to the outdoor m a in
PCB connected correctly?

Power on. Is the error extinguished?

Change the indoor main PCB.

No