beautypg.com

Installation details – Klimaire KSIN Series Service Manual User Manual

Page 22

background image

20

6. Installation details

6.1 Wrench torque sheet for installation

Outside diameter

Torque

Additional

tightening torque

mm

inch

N.cm

N.cm

Ф6.35

1/4

1500

(153kgf.cm)

1600

(163kgf.cm)

Ф9.52

3/8

2500

(255kgf.cm)

2600

(265kgf.cm)

Ф12.7

1/2

3500

(357kgf.cm)

3600

(367kgf.cm)

6.2 Connecting the cables

The power cord of connect should be selected according to the following specifications sheet.

Rated current of appliance

Nominal cross-sectional area (mm)²

>3 and

≤6

0.75

>6 and

≤10

1.0

>10 and

≤16

1.5

>16 and

≤25

2.5

The cable size and the current of the fuse or switch are determined by the maximum current indicated

on the nameplate which located on the side panel of the unit. Please refer to the nameplate before

selecting the cable, fuse and switch.