Klimaire KSIN Series Service Manual User Manual
Page 39
37
4
3
High
Low
1
Medium
1.5
8.4.2.4 Condenser temperature protection
---55℃ at F1.If T3<54℃, the compressor will keep running at the current frequency. ---T3<52℃, the compressor will not limit the frequency and resume to the former frequency. ---T3>60℃ for 5 seconds, the compressor will stop until T3<52℃. 8.4.2.5 Evaporator temperature protection ---T2<0℃, the compressor will stop and restart when T2 >= 5℃. ---0℃≦ T2<4℃, the compressor frequency will be limited and decreased to the lower level ---4℃ ≤T2≤7℃, the compressor will keep the current frequency. ---T2>7℃, the compressor frequency will not be limited.