II. Knock-Down Boiler Assembly

WARNING

Do not apply more than 30 psig to boiler.

WARNING

Any combustion chamber which was damaged

must be replaced immediately.

CAUTION

If heat exchanger is not square on base DO NOT

twist. Carefully lift and reposition.

WARNING

Do not assemble boiler without cerafelt gaskets

between heat exchanger and combustion

chamber. Gaskets must also be between canopy

and heat exchanger.

C.

INSTALLING THE JACKET

1. Before jacket can be secured to boiler assembly

tankless heater coil or blank plate must be attached.

Using rubber gasket and bolts provided secure

heater coil or blank plate to boiler extension

by inserting the bolts from the backside of the

extension. Refer to Figure 4.

A

. REMOVAL OF BOILER.

1. Remove, all boiler to skid, hold down fasteners.

Refer to Figure 3.

2. Carefully walk boiler to the edge of skid. Tilt the

boiler back, allowing an edge to rest on the floor,

and remove the skid.

Figure 3: Base on Skid

B

. TEST HEAT EXCHANGER FOR LEAKS before

proceeding with jacket assembly. Heat exchanger,

canopy, and base are preassembled.
1. Install pressure gauge supplied, a hose to the city

water and a valve in the supply tapping. Plug

remainder of tappings.

2. Fill boiler with water and apply a pressure of at least

10 psig but no more than 30 psig.

Figure 4: Coil Plate Attachment