beautypg.com

Burnham RSA User Manual

Page 33

background image

33

Figure 25: Electrode / Head Setting for

Beckett Burner

Figure 25A: Electrode / Head Setting for

Carlin EZ-HP Burner

Table 7A: Becket AFG Burner

Table 7: Beckett AFG, AF, & SF Burners

Table 7B: Carlin EZ-2HP Burner

Boiler Model

Firing Rate

Manufacturer

GPH

Angle

Type

Head Bar

Air Band Setting

RSA85

.85

Delavan

.75

60°

A

.75

.60

RSAH85

.75

.65

W

.60/.65

.50

RSA110

1.10

.90

.85/1.00

.75

RSAH110

1.00

.85

.60

RSA125

1.25

1.10

A

1.10/1.25

.90

RSAH125

1.10

.90

.85/1.00

.65

RSA135

1.35

1.20

W

1.10/1.25

.85

RSAH135

1.25

1.10

A

.85

Boiler Model

Firing Rate

(GPH)

Hago Nozzle

Air

Settings

Shutter

Band

Head

(stop screw)

Pump Pressure

RSAH85

.75

.65 x 80B

6

0

N/A

140

RSAH110

1.0

.85 x 80B

7

RSAH125

1.1

.90 x 80B

7

RSAH135

1.25

1.0 x 80B

9

Boiler Model

Firing Rate

(GPH)

Hago Nozzle

Air

Settings

Shutter

Band

Head (stop screw)

Pump Pressure

RSA85*

.85

.75 x 80B

10

0

N/A

140

RSA110

1.10

.90 x 80B

8

RSA125

1.25

1.0 x 80B

7

RSA135

1.35

1.10 x 80B

9

RSA170

1.70

1.65 x 80A

7

100

RSA195

1.95

2.00 x 80B

7

RSA240

2.40

2.50 x 80B

7

RSA285

2.85

3.00 x 80B

7

* Equipped with low firing rate baffle