beautypg.com

Burnham RSA User Manual

Page 31

background image

3

Then, press the UP and/or DOWN buttons to

move the set point to the desired value. After 60

seconds without any button inputs, the control will

automatically return to the RUN mode.

Note that L7224 Aquastat Controller will display all

four (4) above-listed adjustment features, but L7248

Aquastat Controller will not display Low Limit and

Low Limit Differential adjustment features.

6.

DISPLAY READOUT

In the RUN mode, the Aquastat will flash "bt"

(boiler temp) followed by the temperature (i.e.,

220), followed by °F or °C.

To read boiler settings, press the I key to read the

parameter of interest. For example, press I High

Limit (HL) is displayed, followed by a three-digit

number, i.e., 220, followed by °F or °C. Pressing

the I button again (on L7224 models) will display

the Low Limit (LL) followed by a three-digit

number and the corresponding degree designator.

See Display Readout, Figure 23.

After approximately 60 seconds without any key

presses, the display will enter a dim display mode.

To return to the bright display mode, simply press

any key.

7. OPERATION
The L7224 model can be in any of four operational

states - Normal, High Limit, Low Limit and Error.

The controller moves back and forth from High

Limit to Normal to Low Limit state as part of

normal operation.

The L7248 model is restricted to three operational

states - Normal, High Limit and Error. The

controller moves back and forth from High Limit to

Normal state as part of normal operation.

For both models, the controller will enter the Error

state when there is an abnormal condition. The

operating states are:
a. Normal: Boiler temperature went below the

High Limit setting (minus the Differential) and

has not exceeded the High Limit setting; or the

boiler temperature went above the Low Limit

setting and has not gone below the Low Limit

setting (minus the Differential).

b. High Limit: Boiler temperature went above the

High Limit setting and has not dropped below

the High Limit setting (minus the Differential).

c. Low Limit: Boiler temperature went below

the Low Limit setting (minus the Low Limit

Differential) and has not gone above the Low

Limit setting.

d. Error: The controller has detected an error

condition (e.g., open sensor) and has shut down

the burner output. The ZC output is energized.

The controller continues to monitor the system

and automatically restarts if the error condition

clears. Refer to Table 4.

Figure 22: L7248/L7224 Circuit Board Layout -

Horizontal Mount

Figure 23: Display Readout Definitions

Table 4: LED Error Codes

Error

Code

Cause / Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM™ wiring.

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; check L1-L2, 110 Vac.

Err6

Fuse; check ECOM wires, replace fuse.

Err7

EEPROM, HL, LL, Hdf, Ldf; reset to default values.

Restore desired settings.

Err8

Repeated B1 fault (voltage present at B1 when out-

put is turned off); check B1 wiring/voltage.

The operating sequence for the L7224/L7248 is

shown in Table 5. See Table 6 for Trouble Shooting

Guide.

8. HIGH LIMIT CONTROLLER

The High Limit opens and turns off the burner

when the water temperature reaches the setpoint.

The High Limit automatically resets after the water

temperature drops past the setpoint and through the