VIII. Service and Cleaning

NOTICE

BURNER SHUTDOWN: Open Service Switch

to turn off burner.
Manual Oil Supply Valve should be closed and

Electric Service to boiler turned off if boiler

will not be operated for an extended period

of time.

A

. General. Inspection service and cleaning should be

conducted annually. Turn off electric power and

close oil supply valve while conducting service or

maintenance.

B

. Firetubes and Combustion Chamber. (See Figure 27)

1. CLEAN THE FIRETUBES

a. Disconnect electric to burner and remove stack.
b. For access to the firetubes, pull top jacket panel

off. Loosen wing nuts, that hold canopy down.

Without taking wing nuts off carriage bolts,

disengage bolts from slots on tubesheet. Pull

canopy off.

c. Remove turbulators.
d. Using a firetube brush clean firetubes. DO

NOT extend brush past the end of the bottom

tubesheet.

e. Assemble the boiler in reverse order.

Units should be cleaned at least once a year, preferably

at the end of each heating season.
It is not necessary to remove burner to clean boiler.
Brush, scrape, or vacuum from top.

Figure 27: Cleaning of RSA Boiler