beautypg.com

Vi. oil piping, Notice – Burnham RSA User Manual

Page 28

background image

28

A

. General.

1. Use flexible oil line(s) so that burner can be

removed without disconnecting the oil supply.

2. A supply line fuel oil filter is recommended as a

minimum for all firing rates but a pleated paper fuel

oil filter is recommended for the lowest firing rate

application to prevent nozzle fouling.

3. Use Flared fittings only. Do not use compression

fittings.

4. Use of a high efficiency micron filter (Garber or

equivalent) in addition to conventional filter is

highly recommended.

VI. Oil Piping

Figure 20: Single-Pipe Installation

B

. Single-pipe Oil Lines.

1. Standard burners are provided with single-stage

3450 rpm fuel units with the bypass plug removed

for single-pipe installations.

2. The single-stage fuel unit may be installed single-

pipe with gravity feed or lift. Maximum allowable

lift is 8 feet. See Figure 20.

NOTICE

Oil piping must be absolutely airtight or leaks or

loss of prime may result. Bleed line and fuel unit

completely.